Resetting The I/O Device To Factory Settings - Siemens SIMATIC ET 200eco PN M12-L System Manual

Distributed i/o system et 200eco pn
Hide thumbs Also See for SIMATIC ET 200eco PN M12-L:
Table of Contents

Advertisement

Maintenance

10.4 Resetting the I/O device to factory settings

Reference
You can find information on the procedure in the Function Manual SIMATIC analog value pro­
cessing (https://support.industry.siemens.com/cs/ww/en/view/67989094).
10.4
Resetting the I/O device to factory settings
Introduction
When you "Reset to factory settings", the I/O device is reset to the "delivery state". All
information that was saved internally on the I/O device is deleted. The I/O device switches to
PROFINET IO mode.
Result after resetting to factory settings
The following table shows an overview of the contents of the saved items after resetting to
factory settings.
Table 10-1  Result after resetting to factory settings
Memory object
IP address
Device name
MAC address
Identification data (I&M0)
Maintenance data (I&M1, 2, 3):
Firmware
Configuration
Parameters
MultiFieldbus
NOTE
Failure of downstream stations is possible
Resetting an I/O device to factory settings can lead to failure of downstream stations in a line.
NOTE
Substitute value behavior of I/O devices when resetting to factory settings
The I/O devices take on the unconfigured state after "Reset to factory settings". There is no I/O
data exchange.
90
Contents
Deleted
(configurable when resetting: "Retain IP address"/
"Delete IP address")
Deleted
Not deleted
Not deleted
Deleted
Not deleted
Deleted
Deleted
Switches to PROFINET IO
Distributed I/O system ET 200eco PN M12-L
System Manual, 11/2023, A5E48753295-AG