Chapter 4
[CA-60] to [CA-84]
[FUP] / [FDN] operations
Code/Name
CA-60
FUP/FDN overwrite
target selection
CA-61
FUP/FDN data save
enable
CA-62
FUP/FDN UDC selection
CA-64
Acceleration time
setting for FUP/FDN function
CA-66
Deceleration time
setting for FUP/FDN function
・ [CA-60] sets as operation target the frequency reference or the PID target
value for 020[FUP]/021[FDN].
・[CA-61] sets whether the modified values of [FUP] / [FDN] should be
saved or not in the inverter nonvolatile memory.
・[CA-62] selects the frequency reference when input terminal 022[UDC] is
ON.
・If [FUP]/[FDN] is turn ON, in the case the frequency reference is changed
you can set the acceleration and deceleration time [CA-64][CA-66].
[F-OP] Speed/Operation change
Code/Name
01(Terminal[Ai1])/02(Terminal[Ai2])/
03(Terminal[Ai3])/04(Terminal[Ai4])/
05(Terminal[Ai5])/06(Terminal[Ai1])/
CA-70
07(Parameter Setting)/
Speed
08(RS485)/09(Option-1)/
reference source
10(Option-2)/11(Option-3)/
selection when
12(Pulse train input(internal))/
[F-OP] is active
13(Pulse train input(option))/
14(Program function)/
15(PID calc.)/16(MOP VR)
CA-71
00([FW]/[RV] terminal)/
RUN
01(3-wire)/02(Keypad's RUN key)/
command source
03(RS485)/04(Option-1)/
selection when
05(Option-2)/06(Option-3)
[F-OP] is active
If input terminal 023[F-OP] is ON, the above settings
are carried out.
Reset terminal [RS]
Code/Name
Range (unit)
00(Always enabled (Trip release at turn-ON))/
01(Always enabled (Trip release at turn-OFF))/
CA-72
02(Only enable in trip status (Trip release at
Reset mode
turn-ON))/
selection
03(Only enable in trip status (Trip release at
turn-OFF))
・Normally, Output is shut off when reset terminal is ON.
It is also possible to enable only trip reset.
Main encoder input
Code/Name
CA-81
Encoder constant setting
CA-82
Encoder phase
sequence selection
CA-83
Motor gear ratio
numerator
CA-84
Motor gear ratio
denominator
・Above parameters set the main encoder input and the
motor gear ratio involved in the encoder feedback.
Initial
Range (unit)
value
00(Speed reference)
00
01(PID1 Set point)
00(No save)/
00
01(Save)
00(0Hz)/
00
01(Save data)
30.00
0.00 to 3600.00(s)
30.00
Initial
Range (unit)
value
Initial
value
00
(For control terminal block [A]/[B])
Range (unit)
Initial value
32 to 65535(pulse)
1024
00(A Phase lead)/
00
01(B Phase lead)
1 to 10000
1 to 10000
For parameter configuration
Pulse train input terminal[A][B]
Code/Name
CA-90
Pulse train input, target
function selection
CA-91
Pulse train input mode
selection
CA-92
Pulse train frequency scale
CA-93
Pulse train frequency filter
time constant
CA-94
Pulse train frequency bias
value
CA-95
Pulse train upper
frequency detection level
CA-96
Pulse train lower
frequency detection level
・When [CA-90] is other than 00, the input terminals [A]/[B]
become pulse train input terminals.
Assign the input terminal function 103[PLA]/104[PLB] to
01
terminals [A]/[B] to perform pulse train input frequency
reference, vector control with encoder feedback or
absolute position control. The pulse train count method
follows the setting of [CA-91].
00
Pulse train input counter
Code/Name
CA-97
Pulse counter compare match
output ON value
CA-98
Pulse counter compare match
output OFF value
CA-99
Pulse counter maximum value
・Set 044[PCMP] to output the compare results of the pulse
train counters of functions 103[PLA]/104[PLB].
・Turning 097[PCC] terminal in ON state resets the counter.
Internal counter
Max. count value
[CA-99]
OFF level [CA-98]
ON level [CA-97]
0
[PLA] input
1
[PCC] input
1
[PCMP] output
4-34
[CA-90] to [CA-99]
Initial
Range (unit)
value
00(Disable)/
01(Reference)/
02(Speed feedback)/
03(Pulse count)
00(90 degrees shift pulse
train)/
01(Forward/Reverse pulse
train and direction
signal)/
02(Forward pulse train and
reverse pulse train)
0.05 to 32.00(kHz)
25.00
0.01 to 2.00(s)
0.10
-100.0 to 100.0(%)
0.0 to 100.0(%)
100.0
0.0 to 100.0(%)
Range
Initial
(unit)
value
0 to 65535
0 to 65535
0 to 65535
65535
00
00
0.0
0.0
0
0