Chapter 4
4.4 Parameter naming (Nomenclature)
AA 1 01
Parameter
group
ー:Common for 1st and 2nd motor
1:1st motor enabled if function [SET] is OFF
2:2nd motor enabled if function [SET] is ON
st
By default, 1
motor parameter is enabled in the case
that 08:[SET] is not assigned in the Intelligent Input
terminals [CA-01] to [CA-11].
Input terminal 024[SET] enable code example.
[SET]OFF
[**-**] type
[**1**] type
(Example)
[SET]OFF
[AH-01]
[Ub-01]
・・・
[Hb102]
[Ab110]
[bA122]
・・・
※When using 2nd motor parameter setting by [SET]
function of terminal, description as 1st motor setting in
the following part is to be replaced with that of 2nd
motor setting.
4.5 Parameter arrangement
Next is the parameter explanation, such as the parameter
group and the internal group number line-up.
T classification numbers "-" and "1" are lined without
distinction, except "2" which is lined-up after "-" and "1".
Example) Regarding the order
[AA101]⇒[AA102]⇒[AA104]⇒[AA105]⇒...
⇒[AA123]⇒[AA201]⇒...⇒[AA223]⇒
[Ab-01]⇒[Ab-03]⇒[Ab110]⇒[Ab-11]⇒...
(Parameters order depends on the last 2 digit.)
⇒[Ab-25]⇒[Ab210]⇒
[AC-01]⇒...
(At first the parameters which middle character is "-"
or "1" are shown, next the parameters which middle
character is "2" are shown, then the group will change.)
※Depending on display restriction function, Parameters
may not be displayed in order.
Refer to [UA-10][UA-21][UA-22].
Internal number
in the group
[SET]ON
[**-**] type
[**2**] type
[SET]ON
[AH-01]
[Ub-01]
・・・
[Hb202]
[Ab210]
[bA222]
・・・
For parameter configuration
4.6 Parameter explanation
・For the motor protection, the following
parameters are necessary to be set.
-[Hb102] to [Hb108](If [IM])
-[Hd102] to [Hd108](If [SM/PMM])
Working
-[bC110](Electronic thermal level setting,
parameters
■Parameter mode (A code)
Frequency reference selection
Code/Name
AA101
Main speed
input source selection,
1st-motor
AA102
Sub speed
input source selection,
1st-motor
AA104
Sub speed setting,
1st-motor
AA105
Speed reference
calculation symbol
selection, 1st-motor
*1)00(Disable)/01(Terminal[Ai1])/02(Terminal[Ai2])/03(Terminal[Ai3])/
04(Terminal[Ai4])/05(Terminal[Ai5])/06(Terminal[Ai6])/07(Parameter
Setting)/08(RS485)/09(Option-1)/10(Option-2)/11(Option-3)/
12(Pulse train input(internal))/13(Pulse train input(option))/
14(Program function)/15(PID)/16(MOP VR)
・To change the frequency input reference, use [AA111].
Example: to set by [FA-01] -> [AA101]=07
To set by Analog(voltage) to set -> [AA101]=01(Ai1)
・To change between main and sub speed is possible with the math
operator.
・If [AA105]=00, the Intelligent input terminal 015[SCHG] can change the
frequency reference input source between the main(OFF) and sub(ON) .
・Through the [AA105] selection, the operator for the main and sub speed
frequency calculation is set.
Temporary frequency addition
Code/Name
AA106
Add frequency
setting, 1st-motor
・When the input terminal 014[ADD] is ON the frequency set in [AA106]
will be temporarily added to the frequency reference.
4-9
[AA101] to [AA106]
1st-motor)
Range (unit)
Initial value
07(JPN)/
01 to 16 *1)
01(EU)(USA)
(ASIA)(CHN)
00 to 16 *1)
00
0.00 to 590.00(Hz)
0.00
00(Disable)/
01(Addition)/
00
02(Subtraction)/
03(Multiplication)
Range (unit)
Initial value
-590.00 to +590.00(Hz)
0.00