Chapter 2
Recommended terminals for wiring
• The following ferrule terminals are recommended for
signal cable for easy wiring and improved reliability of
connectivity.
Ferrule terminal with sleeves
Power cable size
2
mm
(AWG)
0.25 (24)
0.34 (22)
0.5 (20)
0.75 (18)
*) Manufacturer: Phoenix Contact
Wiring procedure
1. Open the insertion hole of the control circuit terminal
block into the socket with a slotted screwdriver (with a
wide of 2.5mm or less).
2. Insert the wire or ferrule terminal into the wire
insertion hole (round) while screwing up with a slotted
screwdriver.
Ferrule terminal
L1 [mm]
Model*
AI 0,25-8YE
4
AI 0,34-8TQ
4
AI 0,5-8WH
4
AI 0,75-8GY
4
2.5mm
・The contral circuit terminal adopts screw type wiring
terminal blocks.
φ
L2 [mm]
d [mm]
12.5
0.8
12.5
0.8
14
1.1
14
1.3
Crimping tool: CRIMPFOX UD 6-4 or CRIMPFOX ZA 3
• Even for pulling out the wire from the socket with a
slotted screwdriver (the insertion hole will be opened).
Insert the wire or ferrule terminal into the wire
insertion hole while screwing up with a slotted
screwdriver.
2-16
Installation and Wiring
φ
D [mm]
2.0
2.0
2.5
2.8