Chapter 4
[AJ-41] to [AJ-52]
PID4 function
Code/Name
AJ-41
00(Disable)/01(Enable)/
PID4
02(Enable (with inverted output)
enable
・The PID4 function is enabled with the above parameter.
・If [AJ-41]=01 when the PID output reaches a negative
value, the PID output is limited to 0.
・If [AJ-41]=02 when the PID output reaches a negative
value, the PID output lets out an inverted output.
・By turning on the 047[PID4] terminal, the PID4 output
becomes 0.
Code/Name
AJ-42
PID4 deviation inversion
PID target
+
value
-
×(-1)
Feedback
・PID4 deviation can be reversed.
Code/Name
AJ-43
PID4 unit selection
AJ-44
PID4 scale adjustment (0%)
AJ-45
PID4 scale adjustment (100%)
AJ-46
PID4 scale adjustment
(decimal point position)
・You can switch the display data and the display unit
involved in the output of the PID control by the
calculation.
Code/Name
AJ-47
PID4 set-point input
source selection
AJ-50
PID4 set-point setting
*2) Adjustable with [AJ-44] [AJ-45] [AJ-46]
・When PID4 target value input is selected, if the selected is
the parameter setting, [AJ-50] gets enabled.
Code/Name
AJ-52
PID4 feedback input
source selection
・Selects the PID4 feedback reference.
*1) 00(Not used)/01(Terminal[Ai1])/02(Terminal[Ai2])/03(Terminal[Ai3])/
04(Terminal[Ai4])/05(Terminal[Ai5])/06(Terminal[Ai6])/07(Parameter
setting)/08(RS485)/09(Option-1)/10(Option-2)/11(Option-3)/12(Pulse
train input (internal)/13(Pulse train input (option)
Initial
Range (unit)
value
00
Initial
Range (unit)
value
00(Disable)/
00
01(Enable)
PID4 deviation
inversion
[AJ-42]
00
PID
deviation
01
Initial
Range (unit)
value
refer <unit table> of
the end of this
01
chapter.
-10000 to 10000
0
-10000 to 10000
10000
0 to 4
2
Initial
Range (unit)
value
00 to 13 *1)
07
-100.00 to 100.00(%)
0.00
*2)
Initial
Range (unit)
value
00 to 06/08 to 13 *1)
01
For parameter configuration
Code/Name
AJ-53
PID4 proportional gain
AJ-54
PID4 integral time constant
AJ-55
PID4 derivative gain
・The PID4 gains are set by the above parameters.
・If input terminal 048[PIDC4] is active (ON), the value of
the integral constant is cleared. If it is done while the
inverter is in running, the driving condition may become
unstable.
Code/Name
AJ-56
PID4 output range
PID output (%)
PID
Target
value
・[AJ-56] Limits the output range of the PID. If [AJ-56] =0.00
the limit is disabled.
Code/Name
AJ-57
PID4 over deviation
level
PID deviation (%)
0%
Output
terminal
ON
091[OD4]
・When the PID deviation pass over ±[AJ-57], the output
terminal function 091[OD4] is activated.
Code/Name
AJ-58
Turn-off level for the PID4
feedback compare signal
AJ-59
Turn-on level for the PID4
feedback compare signal
PID feedback (%)
0%
RUN command
092[FBV4]
ON
・When the PID feedback cross over the [AJ-58] level, the
output terminal 092[FBV4] is OFF. If the PID feedback
crosses under the [AJ-59] level, 092[FBV4] is turned on.
4-24
[AJ-53] to [AJ-59]
Initial
Range (unit)
value
0.0 to 100.0
1.0
0.0 to 3600.0(s)
1.0
0.00
to
0.00
100.00(s)
Range (unit)
Initial value
0.00 to 100.00(%)
0.00
PID output range
[AJ-36]
[AJ-36
Time(s)
Range (unit)
Initial value
0.00 to 100.00(%)
3.00
[AJ-37]
[AJ-37]
ON
Time(s)
Range (unit)
Initial
value
0.00 to 100.00(%)
100.00
0.00 to 100.00(%)
0.00
[AJ-58]
[AJ-59]
Time(s)
ON