Energy zeroCO2 XL Operation Manual page 82

Large storage inverter system
Table of Contents

Advertisement

(green cursor): positive power value which by convention concerns: Production,
(orange cursor ): negative power value which by convention concerns: Purchase
Caution. A cursor color that disagrees with the fl ow directions described above
indicates an incorrect connection direction for the amperometric transformers of the
measuring meters.
Photovoltaic
Moment by moment, it shows the kW produced by the production park.
Fig. 8.4 - Photovoltaic production
Cursor
Direction
outgoing from
photovoltaic
Caution. By defi nition, a generator such as a photovoltaic park can only supply
and not absorb power. Therefore, a cursor of a different color and in the opposite
direction indicates incorrect wiring of the current transformers of the measuring
meters downstream of the inverter.
zeroCO
XL
2
Feed-in, Load absorption, Batteries being charged.
from the mains, Batteries being discharged.
Power
Positive
Description
Meaning
in production
Power output
Work logic and cloud monitoring - 83