Energy zeroCO2 XL Operation Manual page 46

Large storage inverter system
Table of Contents

Advertisement

2. Prepare an AC power cable of the type 3Ph + N + PE.
For L1, L2, L3, N cables without terminal or with tip lugs can be used. For the
grounding part, use eyelet lug with M6 screw hole (Fig. 5.4).
3. Pass the AC power cable inside the slot at the base, proceeding from below
(Fig. 5.5).
Fig. 5.4
4. Connect the grounding cable to the grounding cable plate to the left of the
distribution bars (Fig. 5.6). Secure the eyelet lug with M6 screw. Use torque wrench
respecting the tightening at 9,5 Nm.
Connect the 4 x 3ph + N power cables using the available terminals and respecting
the sequence of the 3 phases (Fig. 5.7). Use torque wrench for clamping the
terminals, respecting the torque indicated on them.
Fig. 5.6
zeroCO
XL
2
Fig. 5.5
Fig. 5.7
Installation - 47