Advertisement

Functions
5.9 Standard machine projects
Requirements
● IO controller supports configuration control for IO systems, for example CPU 1515-2 PN
as of firmware version 1.7
● STEP 7 V13 SP1 or higher
● The rules (Page 241) for the establishment and operation of a standard machine project
have been considered.
Procedure
To set the partner port for a program controlled interconnection, proceed as follows:
1. Select the PROFINET interface of the device (IO controller or IO device) whose port you
want to set.
2. In the properties of the PROFINET interface, select the area "Port interconnection"
(Extended options > Port [...] > Port interconnection).
3. From the drop-down list, select "Setting partner by user program" as partner port.
4. Repeat steps 1 to 3 for each port to be interconnected via the user program.
See also
Customizing arrangement of IO devices in the program (Page 238)
5.9.2.5

Customizing arrangement of IO devices in the program

Requirements
● IO controller supports configuration control for IO systems, for example CPU 1516pro-2
PN as of firmware version 1.7 as an IO controller
● STEP 7 V13 SP1
● At least one partner port was configured as "Partner set by user program".
● The rules (Page 241) for the establishment and operation of a standard machine project
have been considered.
Procedure
The proceedings corresponds to the proceeding for activating optional IO devices.
Only the structure of the data record must be extended for the program-controlled
assignment of the ports. The extension is described in the following sections.
238
PROFINET with STEP 7 V15
Function Manual, 12/2017, A5E03444486-AH