5. Create one of the instructions TSEND_C, TRCV_C or TCON in the program editor.
6. Interconnect the CONNECT parameter of one of the instructions TSEND_C, TRCV_C or
TCON with the tags of the data type TCON_QDN_SEC.
In the example below, the CONNECT parameter of the TCON instruction is
interconnected with the tag "DNS connectionSEC" (data type TCON_QDN_SEC).
Figure 6-14
Additional information
You can find more information on the TCON_QDN_SEC system data type in the STEP 7
online help.
For additional information on secure communication, refer to the section Secure
Communication (Page 36).
6.11.2

Secure OUC of an S7-1500 CPU as TLS server to an external PLC (TLS client)

The following section describes how you can set up Open User Communication via TCP
from an S7-1500 CPU as TLS server to a TLS client.
Setting up a secure TCP connection via the domain name of the communication partner
S7-1500 CPUs as of firmware version V2.0 support secure communication with addressing
via a Domain Name System (DNS).
For secure TCP communication over the domain name you need to create a data block with
the TCON_QDN_SEC system data type yourself, assign parameters and call it directly at
one of the instructions TSEND_C, TRCV_C or TCON.
Communication
Function Manual, 12/2017, A5E03735815-AF
TCON instruction
Open User Communication
6.11 Secure Open User Communication
95