Function rights for the OPC UA server
The corresponding function rights must also be enabled for the users of the server function
on an S7-1500 CPU. It is not enough simply to save the user name and password centrally.
Here is an example to illustrate this type of rights use.
1. Under "Security settings > Users and roles", you define a new role in the "Roles" tab with
the name "PLC-opcua-role-all-inclusive", for example.
2. In the "Categories of function rights" section, you navigate to the runtime rights and then
to the CPU function rights, and select the CPU whose function rights you want to set, for
example PLC_2.
3. You will find the following function right in the "Function rights" section:
– OPC UA server access
The role "PLC-opcua-role-all-inclusive" still needs to be assigned to the relevant users
("Users" tab under "Security settings" in the project tree).
9.3.2.10

Licenses for the OPC UA server

Runtime licenses
A license is required to run the OPC UA server of the S7-1500 CPU. The type of license
required depends on the performance of the respective CPU. The following license types are
differentiated:
● SIMATIC OPC UA S7-1500 small (required for CPU 1511, CPU 1512, CPU 1513, ET
200SP CPUs, CPU 1515SP PC)
● SIMATIC OPC UA S7-1500 medium (required for CPU 1515, CPU 1516, Software
Controller CPU 1507, CPU 1516pro-2PN)
● SIMATIC OPC UA S7-1500 large (required for CPU 1517, CPU 1518)
Communication
Function Manual, 12/2017, A5E03735815-AF
This function right apples on the OPC UA server of the S7-1500 CPU. Only when this
option is selected does a user of the CPU PLC_2 server who has been assigned the
role "PLC-opcua-role-all-inclusive" have the following right: For the establishment of a
session with the server, the user requires client authentication with one of the user
names and corresponding passwords that have been centrally defined (and loaded to
the CPU).
OPC UA communication
9.3 Using the S7-1500 as an OPC UA server
179