Fujitsu AR C72LHTA Series Design & Technical Manual page 77

Table of Contents

Advertisement

NOTES ON INSTALLING CENTRAL DRAIN PAN
Make sure to design and install drain pan to cover the all drain hole on base completely.
The gap between drain pan and base should be less than 2mm.
Be careful of the foot place during the working or design process.
If the foundation or foot place makes working difficult, the metal fittings should be used as
shown below.
Keep in mind that a drain pan not having the recommended outside dimensions can cause a
water leakage or cannot be installed.
Gaps other than the drain holes cause a water leakage. Completely close all the gaps in the
bottom and sides by welding.
The central drain pan shall have
10.8
the width of this value or more.
60.7
Base
38
Foot place
16 or less
620 or more
The central drain pan shall have
the height of this value or more.
Central drain pan
795 or more
Front View
Central
drain pan
672
Left-side View
- (02 - 36) -
10.8
60.7
38
46 or less
Metal fittings
Use metal fittings if necessary.
(Unit : mm)
No gap
Drain pan
No gap