3-2.

WHEN INSTALL NEAR BY UNLIMITED HEIGHT WALL

SINGLE AND MULTIPLE INSTALLATIONS
There are no restrictions on the height of the wall.
The wall (without height restrictions) must not exist on the both sides (left / right) of outdoor
unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
Provide installation spaces other than L3 in accordance with the conditions shown in the
figure below.
Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
larger than 2m.
When installing with the REAR of the outdoor unit facing the wall side
z
Condition
When B ≥ 400 (mm)
When 30 ≤ B < 400 (mm)
Single installation
<Top view>
<Rear>
<Front>
300 mm
or more
200 mm
or more
300 mm
or more
Necessary installation space
L3 ≥ 200 (mm)
L3 ≥ 200 + (400 - B) x 3 (mm)
200 mm
<Rear>
or more
<Front>
300 mm
or more
<Rear>
<Front>
300 mm
or more
Multiple installations
<Top view>
B
B
200 mm 200 mm
- (02 - 08) -
L3
800 mm
or more
Example:
When B is made 200 mm
> =
L3
200+(400-200)×3=800 mm