3-2.
WHEN INSTALL NEAR BY UNLIMITED HEIGHT WALL
SINGLE AND MULTIPLE INSTALLATIONS
There are no restrictions on the height of the wall.
●
The wall (without height restrictions) must not exist on the both sides (left / right) of outdoor
●
unit. Also, must not exist on the both sides (front / rear) of outdoor unit.
Provide installation spaces other than L3 in accordance with the conditions shown in the
●
figure below.
Ventilation resistance can be ignorable when the distance from a wall or product, etc. is
●
larger than 2m.
When installing with the REAR of the outdoor unit facing the wall side
z
Condition
When B ≥ 400 (mm)
When 30 ≤ B < 400 (mm)
Single installation
<Top view>
<Rear>
<Front>
300 mm
or more
200 mm
or more
300 mm
or more
Necessary installation space
L3 ≥ 200 (mm)
L3 ≥ 200 + (400 - B) x 3 (mm)
200 mm
<Rear>
or more
<Front>
300 mm
or more
<Rear>
<Front>
300 mm
or more
Multiple installations
<Top view>
B
B
200 mm 200 mm
- (02 - 08) -
L3
800 mm
or more
Example:
When B is made 200 mm
> =
L3
200+(400-200)×3=800 mm