Troubleshooting - Hussmann Multideck Meat 3750 Installation Manual

Table of Contents

Advertisement

Installation manual
Trouble shooting
issue
Product temperature is higher
than requirement
Products are freezing up
Cabinet exterior is sweating
Lights are not working
________________________________________________________________________________________________________________________
Page 20
possible reason
Store condition is warmer or more humid
than climate class 3 (25°C/60%RH)
Refrigeration plant is not running or
operating at inappropriate settings or
conditions
Evaporator pressure is not set correctly
Insufficient or no air flow appears at the
case air curtain
Case shelf arrangement has been deviated
significantly from original specified setup
Air Return is blocked by merchandise
None of above
Store condition is too cold compared to
design climate class 3
Case evaporator pressure is
lower than specification.
Store humidity is high
Insufficient ventilation
Icon Controller settings (if fitted)
Case SST
No power supply
Lamp fittings (Tombstone, starter
and ballast) are faulty
Lamp failed
Table 1:-
MJPE multideck and SMD/SME Low Height Multideck
Check store air conditioner operation
Check for compressor rack if it is running.
If rack is running and other possible
refrigeration mechanic to check plant
Check suction pressure settings at the case
Check if case fans are turned on or
operating correctly. If any doubt of fan
Check if coil is frozen up. If frozen then
manufacturers guideline or set to suite
the store operating condition. A colder store
duration. A humid store may need
Re-do the shelf arrangement as per
Check store air conditioner operation. If
store condition can not be lifted, then adjust
cabinet evaporator pressure and defrost
Adjust cabinet evaporator pressure
Check store air conditioner operation
Check case ventilation under and at rear of
the case. A fan kit may be needed.
KITS: (Option Extra – ref Page 21)

Troubleshooting

remedial action
reasons are eliminated then call
operation.
and if required adjust as per
case specification
operation contact technician.
check defrost settings as per the
may require longer defrost
more frequent defrost.
the original specification
Remove merchandise to behind
the load limit.
Contact Hussmann
strategy to suite
to suite
Case to Wall: 2500: 96A15-035
3750: 96A15-036
Check settings
SST set too low
Check supply is "on" and light
switch is working.
Call technician to check and
replace in necessary
Replace lamp
Hussmann