Advertisement

"01SET33+015••<CR>"
"01SET33+015••<CR>"
"01SET33+015••<CR>"
"01SET33+015••<CR>"
"01SET33+015••<CR>"
This command sets the setup item 33 (max. relay ON time) of
a controller, identified by the process ID number 01, to 15
minutes. The • • • • • character means blank.
Once the controller has received a command, it answers
with its 2-digit process ID number followed by:
• A A A A A CK
CK
CK (Hex 06)
CK
CK
If the controller recognizes the received command and per-
forms the requested task;
• STX
STX
STX (Hex 02), Data
STX
STX
If the received command is a request of data;
• NAK
NAK
NAK
NAK (Hex 15)
NAK
If the received command is not recognized (e.g. The syntax
is wrong);
• CAN
CAN (Hex 18)
CAN
CAN
CAN
If the controller cannot answer the request (e.g. the pass-
word was not sent, the controller is in setup mode, the setup
item is not available in that model, etc.)
The controller answers to the GET command with the same
Note
data format explained in the SET command.
Following are examples of answers:
"03<STX>+01200<ETX>"
"03<STX>+01200<ETX>"
"03<STX>+01200<ETX>"
"03<STX>+01200<ETX>"
"03<STX>+01200<ETX>"
The controller with process ID number 03 says that its cur-
rent setpoint is +12.00mS.
"01<STX>UE24_21225<ETX>"
"01<STX>UE24_21225<ETX>"
"01<STX>UE24_21225<ETX>"
"01<STX>UE24_21225<ETX>"
"01<STX>UE24_21225<ETX>"
The controller with process ID number 01 says that it is a
HI24212 model with firmware release 2.5.
50
Data
Data, ETX
Data
ETX (Hex 03)
ETX
ETX
Data
ETX