Instruction Manual HI 9931 - HI 9934 Wall Mounted Conductivity & TDS Controllers A L A 4/ 20 0/ 20 O U T P U T A L A S E T L IN E These Instruments are in http://www.hannainst.com Compliance with the CE Directives...
Dear Customer, Thank you for choosing a Hanna Product. Please read this instruction manual carefully before using the instru- ment. This manual will provide you with the necessary information for a correct use of the instrument, as well as a more precise idea of its versatility.
PRELIMINARY EXAMINATION PRELIMINARY EXAMINATION PRELIMINARY EXAMINATION PRELIMINARY EXAMINATION PRELIMINARY EXAMINATION Remove the instrument from the packing material and examine it carefully to make sure that no damage has occurred during shipping. If there is any noticeable damage, notify your Dealer. Note: Save all packing materials until you are sure that the instrument functions correctly.
The recorder output terminals are isolated from the controller circuitry to avoid any interference and are user-switchable between 0 to 20 mA or 4 to 20 mA. The controller is housed in a rugged, modular, fiber-reinforced ABS housing. All models can be wired to work with 110/115V or 220/240V at 50/ 60 Hz power supplies.
Page 5
Fig. 3 Figure 3 is a dimensioned, bottom view of the wall mounted controller. The modular design isolates the control circuitry from the contacts making it possible to make the connections and then close the compartment. Adjustments can then be made only in the control area, without having to open the contacts compartment.
FUNCTIONAL DIAGRAM HI 9931 FUNCTIONAL DIAGRAM HI 9931 FUNCTIONAL DIAGRAM HI 9931 FUNCTIONAL DIAGRAM HI 9931 FUNCTIONAL DIAGRAM HI 9931 FRONT PANEL HI 9931 ALARM 4/20 0/20 mA OUTPUT SET POINT ZERO COARSE FINE SLOPE ALARM AUTO ALARM SET EC FERT.
Page 7
17. Powered dosage terminals (Relay) 18. 110/115V or 220/240V power configuration 19. Incoming power terminals 20. Fuses BOTTOM VIEW 21. Female DIN connector for conductivity probe Unplug the instrument from the power supply before wiring or replacing the fuses.
Page 8
Specifications HI 9931 RANGE 0.00 to 10.00 mS/cm (EC) RESOLUTION 0.01 mS/cm ACCURACY ±2% F. S. (@20 C/68 F) TYPICAL EMC ±2% F. S. DEVIATION CALIBRATION Through "ZERO CAL" and "SLOPE CAL" trimmers SETPOINT RANGE From 0 to 10.00 mS/cm PROPORTIONAL Conductivity from 0.0 to 1.6 mS/cm and CONTROL...
FUNCTIONAL DIAGRAM HI 9934 FUNCTIONAL DIAGRAM HI 9934 FUNCTIONAL DIAGRAM HI 9934 FUNCTIONAL DIAGRAM HI 9934 FUNCTIONAL DIAGRAM HI 9934 FRONT PANEL HI 9934 ALARM 4/20 0/20 mA OUTPUT SET POINT COARSE ZERO FINE SLOPE ALARM AUTO ALARM SET TDS FERT.
Page 10
Open (NO) position. 17. Powered dosage terminals (Relay) 18. 110/115V or 220/240V power configuration 19. Incoming power terminals 20. Fuses BOTTOM VIEW 21. Female DIN connector for TDS probe...
Page 11
Specifications HI 9934 RANGE 0.00 to 1999 ppm (mg/L) RESOLUTION 1 ppm (mg/L) ACCURACY ±2% F. S. (@20 C/68 F) TYPICAL EMC ±2% F. S. DEVIATION CALIBRATION Through "ZERO CAL" and "SLOPE CAL" trimmers SETPOINT RANGE From 0 to 1999 ppm (mg/L) PROPORTIONAL TDS from 0 to 400 ppm and CONTROL...
CONNECTIONS & WIRING CONNECTIONS & WIRING CONNECTIONS & WIRING CONNECTIONS & WIRING CONNECTIONS & WIRING GENERAL POINTS relay terminals relay terminals powered powered • The relay terminals relay terminals relay terminals of the controller are powered powered powered. This means that you can simply hook up your pump or electrovalve directly to the controller and do not need additional power supply.
Page 13
gram). The terminals are powered terminals are powered terminals are powered terminals are powered terminals are powered and hence you do not do not do not do not do not need an external power supply need an external power supply need an external power supply need an external power supply need an external power supply for the pumps or valves.
Page 14
automatic fail-safe secruity automatic fail-safe secruity • The contoller provides for automatic fail-safe secruity automatic fail-safe secruity automatic fail-safe secruity by activating the alarm if there is a power failure, regardless of whether the NC or NO configurations were chosen. •...
MAIN POWER SUPPLY CONNECTION • Before Before connecting the unit to the mains connecting the unit to the mains connecting the unit to the mains connecting the unit to the mains connecting the unit to the mains, make sure Before Before Before controller is completely wired...
CALIBRATION CALIBRATION CALIBRATION CALIBRATION CALIBRATION Make sure that the probe has been properly connected and wired to the controller (see preceding pages) and that the meter is plugged to the mains. Calibration should be ideally performed at a temperature similar to that of the liquid to be monitored. Ensure that the controller is in the “READ”...
• Once the controller is calibrated to a solution by referring to its value at 25 °C, all subsequent measurements are temperature compensated to 25 °C. You can also obtain temperature compen- sation to a different temperature reference point by calibrating the meter to that value.
P R O P O R T I O N A L C O N T R O L P R O P O R T I O N A L C O N T R O L P R O P O R T I O N A L C O N T R O L P R O P O R T I O N A L C O N T R O L P R O P O R T I O N A L C O N T R O L In order to optimize the controlling process and reduce the amount of...
Page 19
and off for 15 seconds. In order to avoid over dosage of highly D mS concentrated chemicals or fertilizers, the 0.80 controller provides even a more accurate 0.60 control. 0.40 0.20 As the graphs show, it does that by 15 30 45 60 15 30 45 60 Seconds stopping the dosage as soon as the cur-...
O V E R D O S A G E T I M E R O V E R D O S A G E T I M E R O V E R D O S A G E T I M E R O V E R D O S A G E T I M E R O V E R D O S A G E T I M E R HI 9931 and HI 9934 provide for an overdosage alarm system.
IMPORTANT: After performing the cleaning procedures rinse the probe thoroughly with distilled or tap water. Dry it and replace the sleeve ensuring that the air-vents are nearer to the cable end and recalibrate the controller. TROUBLESHOOTING If the controller does not respond properly or constantly reads zero or a value close to it, or is in over range, check the probe and cable for cracks.
Page 22
HI 3002 FOR IN-LINE INSTALLATION The drawing illustrates the ideal installation system since the stream pressure in the pipe forces the air bubbles out automatically. HI 3001D illustrated previously can also be ,mounted in this fashion. However the longer stem of HI 3002 facilitates an easier escape route for any air bubbles.
If the repair is not covered by the warranty, you will be notified of the charges incurred. If the instrument is to be returned to Hanna Instruments, first obtain a Returned Goods Authorization Number from the Cus- tomer Service department and then send it with shipment costs prepaid.