Factory Reset - Biasi BASICA COND 28S User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for BASICA COND 28S:
Table of Contents

Advertisement

the 15 and 16 keys simultaneously for 5
seconds (Fig. 8.25) until the code P00 ap-
pears on the display, indicating entry into
"parameter P00" (Fig. 8.26).
16
10
11
Fig. 8.25
Fig. 8.26
• Scroll through the various menus by
pressing the keys 10 (back) or 11 (for-
ward), until the LCD display shows the
code P05, indicating entry into "parameter
P05" (Fig. 8.27).
Fig. 8.27
• Press the keys 14, until the value of pa-
rameter P05 on the LCD display (Fig.
8.28).
ADVANCED COMMISSIONING
15
14
13
12
RESET
bar
RESET
bar
Fig. 8.28
• It is possible to modify the value of param-
eter 05 from 0 to 255 minutes by pressing
the 13 or 14 keys.
• Press 10 or 11 (Fig. 8.21) to confirm the
value entered and return to the list of pa-
rameters (Fig. 8.23).
• Press the 15 button (Fig. 8.21) to exit "pro-
gramming mode".
8.8

Factory reset

The RESET returns all parame-
ters to the factory settings.
• Enter "programming mode" by following
the steps described in the section "Access
parameters for installer" on page 49.
16
10
11
Fig. 8.29
• Press 10 and hold until the LCD display
shows the code A49, indicating entry into
"parameter A49" (Fig. 8.30).
RESET
bar
15
14
13
12
- 55 -