Servo Motor With Electromagnetic Brake - Mitsubishi Electric MR-J2S B Series Instruction Manual

Servo amplifier
Table of Contents

Advertisement

3. SIGNALS AND WIRING

3.7 Servo motor with electromagnetic brake

CAUTION
Note the following when the servo motor equipped with electromagnetic brake is used.
1) Do not share the 24VDC interface power supply between the interface and electromagnetic
brake. Always use the power supply designed exclusively for the electromagnetic brake.
2) The brake will operate when the power (24VDC) switches off.
3) Switch off the servo-on command after the servo motor has stopped.
(1) Connection diagram
Servo amplifier
VDD
COM
MBR
(2) Setting
In parameter No.21 (electromagnetic brake sequence output), set the time delay (Tb) from
electromagnetic brake operation to base circuit shut-off at a servo off time as in the timing chart in (3)
in this section.
Configure the electromagnetic brake circuit so that it is activated not only by the
interface unit signals but also by a forced stop (EM1).
Contacts must be open when
servo-off, when an alarm occurrence
and when an electromagnetic brake
interlock (MBR).
The electromagnetic brake is provided for holding purpose and must not be used
for ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake
operates properly.
POINT
Refer to the Servo Motor Instruction Manual for specifications such as the
power supply capacity and operation delay time of the electromagnetic
brake.
24VDC
RA
Servo motor
RA
EM1
Electromagnetic brake
Forced
stop
RA
B1
B2
3 - 22
Circuit must be
opened during
forced stop (EM1).
24VDC
Servo motor

Advertisement

Table of Contents
loading

Table of Contents