AHU-KIT
NOTICE
9~144 kBtu/h units can be connected to the same system; 72~288 kBtu/h units can be
connected to the same system.
(3) Connection method 3: one-to-more (mixed connection)
The AHU-KIT as below can adopt one-to-more connection method with general VRF indoor
unit. Total capacity of AHU-KIT and VRF indoor unit should be 50%~110% of that of outdoor unit.
Total capacity of AHU-KIT cannot exceed 30% of that of outdoor unit.
GMV-N12U/C-T(U)
GMV-N24U/C-T(U)
GMV-N48U/C-T(U)
GMV-N96U/C-T(U)
NOTICE
When connecting AHU-KIT with general VRF indoor unit, capacity requirement shall be
followed strictly. Otherwise, it may affect the operation, or even damage the unit.
Fig.2.5.1 AHU-KIT one-to-one (single unit) connection diagram
Model
Capacity in application (kBtu/h)
8
9
12
15
18
24
30
36
48
60
72
96