Time Clock; Modulating Outputs - TCS SuperSTAT SZ1053 Configuration Manual

Communicating thermostat
Hide thumbs Also See for SuperSTAT SZ1053:
Table of Contents

Advertisement

Configuration

Time Clock

STEP 1
Time Clock Output: Select whether the auxiliary output will be
OPEN during occupied periods and closed during unoccupied
periods, or CLOSED during occupied periods and open during
unoccupied periods.

Modulating Outputs

STEP 1
Output 1 Proportional Band: Enter the number of degrees
away from the heating setpoint that the valve or damper will be
fully open.
STEP 2
Output 2 Proportional Band: Enter the number of degrees
away from the heating setpoint that the valve or damper will
be fully open
STEP 3
Output 1 Setpoint Offset: Enter the number of degrees below
the heating setpoint before the output begins to modulate.
STEP 4
Output 2 Setpoint Offset: Enter the number of degrees below
the heating setpoint before the output begins to modulate.
STEP 5
Output 1 Action: Select whether the output will be direct or
reverse acting.
STEP 6
Output 2 Action: Select whether the output will be direct or
reverse acting.
STEP 7
Output 1 Range: Select whether the range will be 0 – 20mA
or 4 – 20mA.
STEP 8
Output 2 Range: Select whether the range will be 0 – 20mA
or 4 – 20mA.
STEP 9
Output 1 Unoccupied Action: Select whether the unoccupied
action will be 0mA, 4mA, 20mA, or modulating.
8
2800 Laura Lane
Middleton, WI 53562
TIME CLOCK OUTPUT
OCCUPIED = OPEN
MO1 PROPORTIONAL
BAND
MO2 PROPORTIONAL
BAND
MO1 SETPOINT
OFFSET
MO2 SETPOINT
OFFSET
MOD OUT 1
ACTION:
MOD OUT 2
ACTION:
MOD OUT 1
RANGE
MOD OUT 2
RANGE
MOD OUT 1 UNOCC
ACTION:
|
800.288.9383
|
www.tcsbasys.com
04F
04F
00F
00F
DIRECT
DIRECT
4-20MA
4-20MA
MOD

Advertisement

Table of Contents
loading

This manual is also suitable for:

Superstat sz1051

Table of Contents