TCS SuperSTAT SZ1053 Configuration Manual page 9

Communicating thermostat
Hide thumbs Also See for SuperSTAT SZ1053:
Table of Contents

Advertisement

Configuration
STEP 10 Output 2 Unoccupied Action: Select whether the unoccupied
action will be 0mA, 4mA, 20mA, or modulating.
STEP 11 Discharge Air Sensor: Select whether to use a discharge air
sensor. To monitor only, select NO.
NOTE:
Refer to the
Manual
for dip switch settings, which must also be set
STEP 12 Discharge Air Low Limit: Enter a discharge air low-limit value:
NOTE:
This screen appears only if the discharge air sensor
function is enabled (Step 11).
STEP 13 Discharge Air High Limit: Enter a discharge air high-limit
value:
NOTE:
This screen appears only if the discharge air sensor
function is enabled (Step 11).
STEP 14 Output 1 Control: Select whether to control the modulating
output based on DISCHARGE air reset or SPACE temperature.
STEP 15 Output 2 Control: Select whether to control the modulating
output based on DISCHARGE air reset or SPACE temperature.
STEP 16 Heating Low Limit: Select whether to enable Heating Low-
Limit.
STEP 17 Output 1 Discharge Air Setpoint: Enter the discharge air
heating setpoint.
STEP 18 Output 2 Discharge Air Setpoint: Enter the discharge air
cooling setpoint.
STEP 19 Output 1 Reset Ratio: Enter the degrees that the discharge
air setpoint is raised when the space temperature falls by 1
degree.
STEP 20 Output 2 Reset Ratio: Enter the degrees that the discharge
air setpoint is raised when the space temperature rises by 1
degree.
9
9
SZ1051/1053 SuperSTAT Installation
2800 Laura Lane
Middleton, WI 53562
MOD OUT 2 UNOCC
ACTION:
ENABLE DISCHARGE
AIR FUNCT.?
DISCHARGE AIR
LOW LIMIT:
DISCHARGE AIR
HIGH LIMIT:
MOD OUT 1 BASED
ON:
MOD OUT 2 BASED
ON:
ENABLE HEATING
LOW LIMIT
MO 1 DISCHARGE
SETPOINT:
MO 2 DISCHARGE
SETPOINT:
MO 1 RESET RATIO
FACTOR:
MO 2 RESET RATIO
FACTOR:
|
800.288.9383
|
www.tcsbasys.com
MOD
YES
045F
125F
DISCHARGE
DISCHCHARGE
NO
90F
60F
2.0F
2.0F

Advertisement