Installation
Packaged Unit Terminations
Packaged unit signals may be up to 28VAC from the equipment terminations.
R
W1 W2
Y1
Y2
G
B/O
TC
AO1 AO2 GND
A
B
REF
+
24V
–
DI1
DI2
DI3 GND
T1
T2
T3
+P AI1
AI2 GND
Time Clock Output
The Time Clock Output is an unpowered, isolated pair of relay contacts. Connect an external device that operates with a
schedule based on room occupancy, such as an outdoor air dampener or exhaust fan. Use 18 – 22AWG two-wire twisted,
stranded shielded or unshielded wire.
'10
'20
'40
Analog Outputs
Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the UbiquiSTAT. If you desire a voltage output,
use an included 500Ω resistor.
AO1
AO2
GND
6
R
W1
W2
Y1
R
W1 W2
'20
'50
+ –
*
AO1 AO2 GND
'10
2800 Laura Lane • Middleton, WI 53562 | 800.288.9383 | www.tcsbasys.com
Y2
G
B/O
Y1
Y2
G
B/O
TC
'40
'50
or
B/O
TC
+ –
+ –
* = Optional
500Ω Resistor
AO1 AO2 GND
'50
R
W1
Y1
R
W1 W2
Y1
Y2
G
'10
24VAC
+
–
B/O
TC
*
'40
G
B/O
B/O
TC