Installation

Packaged Unit Terminations

Packaged unit signals may be up to 28VAC from the equipment terminations.
R
W1 W2
Y1
Y2
G
B/O
TC
AO1 AO2 GND
A
B
REF
+
24V
DI1
DI2
DI3 GND
T1
T2
T3
+P AI1
AI2 GND

Time Clock Output

The Time Clock Output is an unpowered, isolated pair of relay contacts. Connect an external device that operates with a
schedule based on room occupancy, such as an outdoor air dampener or exhaust fan. Use 18 – 22AWG two-wire twisted,
stranded shielded or unshielded wire.
'10
'20
'40

Analog Outputs

Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the UbiquiSTAT. If you desire a voltage output,
use an included 500Ω resistor.
AO1