Installation
HVAC Unit Terminations
HVAC unit signals may be up to 28VAC from the equipment terminations.
R W/Y1 W/Y2 G
Y2
–
+
24V
DI1
DI2
DI3 OVR T1
Time Clock Output
The Time Clock Output is an unpowered, isolated pair of relay contacts. Connect an external device that operates with a
schedule based on room occupancy, such as an outdoor air damper, exhaust fan, or a dehumidification/reheat unit. Use
18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
R W/Y1 W/Y2 G
Y2
–
+
24V
DI1
DI2
DI3 OVR T1
Analog Outputs
Connect 4 – 20mA, analog output devices using 18 – 22AWG two-wire twisted, stranded shielded or unshielded wire.
Connected actuators, motors, or drives must be powered separately from the SuperSTAT. If you desire a voltage output,
use an included 500Ω resistor.
R W/Y1 W/Y2 G
Y2
–
+
24V
DI1
DI2
DI3 OVR T1