Daikin FTXP20-71L Service Manual page 54

Table of Contents

Advertisement

3
|
Components
To perform an electrical check of the compressor
Service manual
54
a
a Damper
INFORMATION
The compressor dampers may look different.
Compressor dampers are in a good
condition?
Yes
No
1 First perform a mechanical check of the compressor, see
4
procedures" [
 52].
DANGER: RISK OF ELECTROCUTION
Wait for at least 10 minutes after the circuit breaker has been turned OFF, to be sure
the rectifier voltage is below 10 V DC before proceeding.
2 Remove the cover of the compressor wire terminals.
a
Action
Perform an electrical check of the
compressor, see
"3.2.1 Checking
4
procedures" [
 52].
Replace the compressor and/or
damaged dampers, see
4
procedures" [
 58].
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
"3.2.2 Repair
"3.2.1  Checking
Split Comfora R32
ESIE18-01E – 2023.01