Daikin FTXP20-71L Service Manual page 104

Table of Contents

Advertisement

3
|
Components
Problem solved?
Repair procedures
To remove the propeller fan blade assembly
Service manual
104
INFORMATION
Winding resistance values above are given for reference. You should NOT be reading
a value in kΩ or a short‑circuit. Make sure that the propeller fan blade does NOT
rotate, as this could affect resistance measurements.
9 Set the Megger voltage to 500 V DC or 1000 V DC.
10 Measure the insulation resistance for the motor terminals. Measurements
between each phase and fan motor body (e.g. axle) MUST be >1000 MΩ.
Are the measured resistance values
correct?
Yes
No
After all checking procedures listed above have been performed:
Is the problem solved?
Yes
No
Prerequisite: Stop the unit operation via the user interface.
Prerequisite: Turn OFF the respective circuit breaker.
1 Remove the required plate work, see
2 Remove the nut that fixes the propeller fan blade assembly.
a Nut
b Propeller fan blade assembly
3 Pull and remove the propeller fan blade assembly from the DC fan motor
assembly.
Action
Perform a check of the main PCB, see
"3.7.1 Checking
Replace the DC fan motor, see
procedures" [
Action
No further actions required.
Return to the troubleshooting of the
specific error and continue with the
next procedure.
"3.9 Plate
work" [
a
b
ATXP20~35 + FTXP20~71 + ARXP20~35 + RXP20~71
4
procedures" [
 84].
"Repair
4
 104].
4
 111].
Split Comfora R32