Installation and Operation Guide SOLECTRIA

AC Connections

The AC connections consist of the 3 AC Phases (L1, L2, and L3) and Ground. AC wires must be rated for at
least 600 VAC. Use wires within the ranges shown in Table 3-2, and sized as required to comply with local
codes and the National Electrical Code.
AC Output Conductors
(L1, L2, L3)
Neutral (Bonded to
Ground)
Turn the AC Switch OFF before wiring. Wire the AC Connections as shown in Figure 3-143.
For the AC connections, use compression lugs with a single hole for a ½ in or M12 stud and sized for the wire
gauge used. The width of the lugs must be 1.5 in (38 mm) or less. Torque to 220 in-lbs (25 N-m) using an
18mm socket and torque driver. A hex nut and washer are provided. The terminal block accepts single or
parallel conductor sets. See Figure 3-13 for the hardware assembly instructions.
DOCR-071074 (Rev 7, 30 MAY 2023)
Table 3-2 AC Connection Specifications
Electric Shock Hazard
Components with hazardous voltage and energy will electrocute the operator.
Ensure AC power doesn't flow into inverter. Verify with a multi-meter.
®
XGI 1500-250 Series Inverters
XGI 1500-250/250-600, XGI 1500-225-600
XGI 1500-200/200-480, XGI 1500-175-480
Range Allowed
Cu and Alum: Min: Per NEC
Max: 600 kcmil, 1 or 2 conductors with lugs
Range Allowed
Cu and Alum: Min: Per NEC
Max: 1/0 AWG
22 of 72