YASKAWA SOLECTRIA XGI 1500-250/250-600 Installation And Operation Manual page 54

Utility scale 1500vdc string inverter
Table of Contents

Advertisement

Installation and Operation Guide SOLECTRIA
AC Very High
8
Frequency 2
Detected
AC Low Voltage
9
1 Detected
AC Very Low
10
Voltage 2
Detected
AC Extremely
11
Low Voltage 3
Detected
AC High Voltage
12
1 Detected
AC Very High
13
Voltage 2
Detected
...
Communication
25
1 Fault
Communication
26
2 Fault
DOCR-071074 (Rev 7, 30 MAY 2023)
®
XGI 1500-250 Series Inverters
AC high frequency region 2
detected.
AC low voltage region 1 detected.
AC low voltage region 2 detected.
AC low voltage region 3 detected.
AC high voltage region 1
detected.
AC high voltage region 2
detected.
Communication processor
initialization fault.
Communication processor
application fault.
Using a CAT III multi-meter verify the
AC frequency. If there is a discrepancy
of greater than 2% between the
measured results and the frequency
reported by the inverter contact
Technical Support, otherwise wait for
the grid conditions to improve.
Using a CAT III multi-meter verify the
AC voltage. If there is a discrepancy of
greater than 2% between the measured
results and the voltage reported by the
inverter contact Technical Support,
otherwise wait for the grid conditions to
improve.
Using a CAT III multi-meter verify the
AC voltage. If there is a discrepancy of
greater than 2% between the measured
results and the voltage reported by the
inverter contact Technical Support,
otherwise wait for the grid conditions to
improve.
Using a CAT III multi-meter verify the
AC voltage. If there is a discrepancy of
greater than 2% between the measured
results and the voltage reported by the
inverter contact Technical Support,
otherwise wait for the grid conditions to
improve.
Using a CAT III multi-meter verify the
AC voltage. If there is a discrepancy of
greater than 2% between the measured
results and the voltage reported by the
inverter contact Technical Support,
otherwise wait for the grid conditions to
improve.
Using a CAT III multi-meter verify the
AC voltage. If there is a discrepancy of
greater than 2% between the measured
results and the voltage reported by the
inverter contact Technical Support,
otherwise wait for the grid conditions to
improve.
Power cycle the inverter. If the inverter
doesn't clear the error, contact
Technical Support.
Power cycle the inverter. If the inverter
doesn't clear the error, contact
Technical Support.