Equipment Grounding

Improper Transformer Configuration
Inverter will not run and may have hazardous current. Connect transformer in specified
configurations only. Incorrect transformer configuration may cause damage to the inverter.
The XGI 1500 must be bonded using equipment grounding provisions. Do not attempt to ground either DC
pole. The XGI 1500 includes provisions for terminating equipment grounding conductors and other conductors
used for bonding. One M8 stud with an M8 external-tooth star nut is located inside the inverter wiring section
(Figure 3-122). Use a 13mm socket and torque to 90 in-lbs (12.2 N-m). On the exterior of the inverter is an M6
threaded insert (Figure 3-122) Torque this customer-supplied fastener to 39 in-lbs (4.4N-m)
M8 Stud
and Nut
Figure 3-12 Ground Connection Inside and Outside Inverter and Neutral Lug
XGI 1500-250/250 XGI 1500-225
Equipment
Ground
Conductor
DOCR-071074 (Rev 7, 30 MAY 2023)
Table 3-1 Grounding and Bonding Connection Specifications
Copper: 4 AWG to 1/0 AWG
Aluminum: 2 AWG to 1/0 AWG
®
XGI 1500-250 Series Inverters
Neutral
Lug
M6
Threaded
Insert
XGI 1500-200/200 XGI 1500-175