Do not use any metallic tools within the cooling plenum as this could damage the
insulation on the inductors.
To clean the cooling plenum:
1. Turn off the inverter, first by moving the DC Switch on the inverter to the "OFF" position, then by turning
the AC Switch on the inverter to the "OFF" position.
2. Close the inverter cover and secure all latches before re-energizing the inverter
3. Use a vacuum with a non-metallic nozzle to remove the debris from air plenum, heatsink, and
inductors. Use a stiff nylon brush to loosen any stubborn debris.
4. Replace the cover before re-energizing the inverter.
Failure to keep the inverter properly maintained may cause permanent damage not
covered under warranty.
DOCR-071074 (Rev 7, 30 MAY 2023)
®