Option
SEG 7
Function
Page
Indication
Details
Indication
and details
1
DB68-11271A-02_IM_CAC Universal AHU Indoor_AA_EN_.indd 53
SEG 8
SEG 9
Use of drain pump
Use of Hot Coil
Indication
Details Indication Details Indication Details
0
Disuse
0
Disuse
1
Use
1
Use
Use
with 3
2
minute
delay
SEG 10
SEG 11
Use of Hot auxiliary
Controller variables for auxiliary
heater
heater
Details
Set
Indication
temperature
for auxiliary
heat on
No temperature
0
offset
0
Disuse
No temperature
1
offset
No temperature
2
offset
3
2.7°F(1.5°C) No delay
4
2.7°F(1.5°C)
5
2.7°F(1.5°C)
5.4°F(3°C) No delay
6
1
Use
7
5.4°F(3°C)
8
5.4°F(3°C)
9
8. 1 °F(4.5°C) No delay
A
8. 1 °F(4.5°C)
B
8. 1 °F(4.5°C)
Use
(Heater
2
C
10.8°F(6°C) No delay
time
delay)
D
10.8°F(6°C)
E
10.8°F(6°C)
SEG 12
Time
delay for
auxiliary
heat on
No delay
10
minutes
20
minutes
10
minutes
20
Reserved
minutes
10
minutes
20
minutes
10
minutes
20
minutes
10
minutes
20
minutes