MULTI AIR CONDITIONER INDOOR UNIT OUTDOOR UNIT AR07/15CSDAFWKN AJ020BXJ2CH AR09/12/18/24CSDABWKN AJ024BXJ3CH AR07/09/12/15/18/24CSFCMWKN AJ036BXJ4CH AR07/09/12/15/18/24CSKCPWKN AJ048BXJ5CH AC009/012/018BNNDCH AJ020CXS3CH AC009/012/018BNLDCH AJ024CXS4CH AJ009/012/015/018BNHDCH AJ030CXS4CH AC009/012BN1DCH AJ036CXS4CH AC009/012/015/018BNJDCH AC012/018/024BNZDCH AIR CONDITIONER CONTENTS 1. Precautions 2. Product Specifications 3. Disassembly and Reassembly 4. Troubleshooting 5. PCB Diagram 6.
Page 2
"look and feel" and arrangement of such Content, contained in this manual is owned, controlled or licensed by or to Samsung, and is protected by trade dress, copyright, patent and trademark laws, and various other intellectual property rights and unfair competition laws.
Contents 1. Precautions······························································································································1-1 1-1 Precautions for the Service ......................1-1 1-2 Precautions for the Static Electricity and PL................. 1-1 1-3 During operation ..........................1-2 1-4 Disposing of the unit ........................1-2 1-5 Precautions for the Pump Down ..................... 1-2 1-6 Others ..............................1-2 2.
Page 4
Contents 4-6-5 Compressor startup error, Compressor lock error, Compressor rotation error ....4-48 4-6-6 IPM Over current error ......................4-49 4-6-7 Checking Temperature sensor ....................4-50 4-7 PCB Inspection ..........................4-52 4-7-1 Cautions for Part Replacement ....................4-52 4-7-2 Procedure ............................. 4-52 5.
>3mm. • Do not extend an electric cord to the air conditioner. No Tapping and No Extension Cords • The air conditioner must be plugged in after you complete the installation. Samsung Electronics...
• Current is measured according to ISO standard for energy efficiency. • For servicing the units containing flammable refrigerants, safety checks are required to minimise the risk of ignition. • Servicing shall be performed following the controlled procedure to minimize the risk of flammable refrigerant or gases. Samsung Electronics...
■ Universal Connection Multi Inverter(Free Joint Multi) Series delivers comfort to 2~5 rooms with a Single Outdoor Unit. Free Joint Multi added Universal indoor units, which can be universally connected to other Samsung outdoor units, to all lineup. ■ Various Indoor units & combinations ·...
Page 8
When you want to operate all indoor units with the cooling mode or heating mode. ■ Wi-Fi Fuction (SmartThings app) SmartThings app is the easy way to turn your home into a smart home. Control the FJM with only one application. This feature is optional to the several models. Samsung Electronics...
Page 10
Cross flow fan Cross flow fan Cross flow fan Type BLDC BLDC BLDC Part Fan Motor Code DB31-00636A DB31-00636A DB31-00636A Row, Heat Exchanger 2Rx16S 2Rx16S 2Rx16S Step Refrigerant Control Device EEV NOT INCLUDED EEV NOT INCLUDED EEV NOT INCLUDED Samsung Electronics...
Page 11
Cross flow fan Cross flow fan Cross flow fan Type BLDC BLDC BLDC Part Fan Motor Code DB31-00636A DB31-00636A DB31-00636A Row, Heat Exchanger 2Rx16S 2Rx16S 2Rx16S Step Refrigerant Control Device EEV NOT INCLUDED EEV NOT INCLUDED EEV NOT INCLUDED Samsung Electronics...
Page 12
9.52 Type Turbo Fan Turbo Fan Turbo Fan Type BLDC BLDC BLDC Part Fan Motor Code DB31-00578C DB31-00578C DB31-00578C Row, Heat Exchanger 2Rx8S 2Rx8S 2Rx8S Step Refrigerant Control Device EEV NOT INCLUDED EEV NOT INCLUDED EEV NOT INCLUDED Samsung Electronics...
Page 13
Cross Flow FAN Type BLDC BLDC BLDC BLDC Part Fan Motor Code DB31-00639B DB31-00639B DB31-00639B DB31-00639B Row, Heat Exchanger 3Rx16S 3Rx16S 3Rx16S 3Rx16S Step Refrigerant Control Device EEV NOT INCLUDED EEV NOT INCLUDED EEV NOT INCLUDED EEV NOT INCLUDED Samsung Electronics...
Page 14
15.88 Type Sirroco FAN Sirroco FAN Sirroco FAN Type BLDC BLDC BLDC Part Fan Motor Code DB81-05891A DB81-04294H DB81-04294J Row, Heat Exchanger 2Rx24S 3Rx24S 3Rx24S Step Refrigerant Control Device EEV NOT INCLUDED EEV NOT INCLUDED EEV NOT INCLUDED Samsung Electronics...
Product Specifications 2-4 Combination Table (Outdoor-Indoor) Design Model Name Model AJ020BXJ2CH AJ024BXJ3CH AJ036BXJ4CH AJ048BXJ5CH AJ020CXS3CH AJ024CXS4CH AJ030CXS4CH AJ036CXS4CH Capacity Model [kBtu/h] AR07CSDAFWKN 7/9/12 ● ● ● ● ● ● ● ● AR09/12CSDABWKN AR15CSDAFWKN ● ● ● ● ● ● ●...
Page 20
Not Allowed Allowed Allowed ≤ 1.0 JXH30S4C (AJ030CXS4CH/AA) Not Allowed Not Allowed Allowed Allowed ≤ 1.0 JXH36S4C (AJ036CXS4CH/AA) Not Allowed Not Allowed Allowed Allowed ≤ 1.0 *Mixed installation means mixing AJ***BNHDCH/AA and AC***BNZDCH/AA units on the same system. 2-14 Samsung Electronics...
2) Loosen each 9 screws(CCW) on Cabi-Top. (Use +Screw Driver). 3) Loosen 2 screws(CCW) fixed to assemble Plate Control Out with Cabinet-Side RH. (Use +Screw Driver.) 4) Loosen 10 fixing screws(CCW) on Cabinet- Side RH. (Use +Screw Driver.) Samsung Electronics...
Page 29
(Use +Screw Driver.) Ass’y 1) Detach the Motor Wire from the PCB of Control Out Ass'y Control Out. 2) Detach comp wire and pressure switch- wire from the PCB of A’ssy Control Out. 3) Detach 2 Connect Wires from Reactor. Samsung Electronics...
Page 30
4) Detach the Heat Exchanger. Befor you disassemble the pipes and Condensor, be sure that there should be no refrgerant remained in the unit. 5) Loosen 3 nuts of the Compressor. (Use Monkey Spanner.) 6) Detach the Compressor. Samsung Electronics...
1) Loosen 6 fixing screws (CCW) on the Cabinet-Side RH. (Use +Screw Driver). Cabi Front RH 1) Loosen 3 fixing screws (CCW) on the Cabinet-Front RH. (Use +Screw Driver). Cabi Top 1) Loosen 7 or 9 fixing screws (CCW) on the Cabi-Top. (Use +Screw Driver). Samsung Electronics...
Page 32
Gurad Cond. (Use +Screw Driver). Cabi Back RH 1) Detach the Sensor from the Cabi-Back 2) Loosen 5 fixing screws (CCW) on Cabi- Back RH. (Use +Screw Driver). 3) Pull the hook of Cabi Back RH from the Bracket Valve. Samsung Electronics...
Page 33
Parts Procedure Remark Plate Case Control 1) Loosen 2 fixing screws (CCW) on the Plate Support Case Control Support. (Use +Screw Driver). Cabi Front LF 1) Loosen 10 fixing screws (CCW) on the Cabinet-Front LF. (Use +Screw Driver). Samsung Electronics...
Page 34
1) Detach the Motor Wire from PCB of A’ssy Control Out. 2) Loosen 4 fixing bolts (CCW) and detach the Motor. (Use +Screw Driver.) Backet Motor 1) Loosen 2 fixing screws (CCW) and detach the Bracket Motor. (Use +Screw Driver.) Samsung Electronics...
Page 35
Disassembly and Reassembly Parts Procedure Remark Control Out 1) Detach Comp-Wire and Pressure-Wire from PCB of A’ssy Control Out. 2) Loosen 4 fixing screws (CCW) and detach the Bracket Motor. (Use +Screw Driver.) 3) Separate A’ssy Control Out. Samsung Electronics...
Page 36
1) Disassemble the pipes in both inlet and outlet with welding torch. 2) Loosen 2 fixing screws (CCW) and detach the Bracket Valve. (Use +Screw Driver.) Compressor 1) Loosen fixing nut (CCW) on the Cover- Terminal. (Use Monkey Spanner or adjust- able Wrench.) 3-10 Samsung Electronics...
Page 37
When assembling Comp Wire, make sure to match the color and location of the wire with the picture. Heat Exchanger 1) Loosen 2 fixing screws(CCW) on both sides. And loosen 1 fixed screws(CCW) Partition with base.(Use +Screw Driver.) Samsung Electronics 3-11...
2) Remove the 4 screws from the Cabinet Front RH and separate it. (Use + Screw Driver) Cabinet Top 1) Remove the 8 screws which is fixed to each side of cabinet top and separate it. (Use + Screw Driver) 3-12 Samsung Electronics...
Page 39
Cabinet Back RH 1) Pull out the sensor from the cabinet back RH and separate it. 2) Remove the 4 screws which is fixed to each side cabinet back RH and separate it. (Use + Screw Driver) Samsung Electronics 3-13...
Page 40
Plate Control 1) Remove the 1 screw from the Plate Conrtol and separate it. (Use + Screw Driver) Cabinet Front LH 1) Remove the 10 screws from the canbinet Front LF and separate it. (Use + Screw Driver) 3-14 Samsung Electronics...
Page 41
Disassembly and Reassembly Parts Procedure Remark Cabinet Front LH 1) Remove the 2 fixing nuts like the picture on the right side. (Use Hexagon Wrench, Monkey Spanner, Hexagon Socket) Samsung Electronics 3-15...
Page 42
Motor. ( Use + Screw Driver ) 3) Separate the Motor Wire connector from the Outdoor Unit Control Part. Bracket Motor 1) Remove the 2 screws from the Bracket Motor and separate it. (Use + Screw Driver) 3-16 Samsung Electronics...
Error due to connecting outdoor units that do not support the WindFree function : On : Flickering x: Off • If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 44
Outdoor valve clogging error Miss matching error between indoor unit and outdoor unit : On : Flickering x: Off - If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 45
(Communication error for more than 2 minutes) : On : Flickering x: Off - If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 46
EEPROM error E162 EEPROM option error E163 Error due to incompatible indoor unit E164 : On : Flickering x: Off - If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
Page 47
2 minutes) : On : Flickering x: Off - If you turn off the air conditioner when the LED is flickering, the LED is also turned off. Samsung Electronics...
ERROR ON PIPE IN-C TEMPERATURE SENSOR(SHORT OR OPEN) E333 ERROR ON PIPE IN-D TEMPERATURE SENSOR(SHORT OR OPEN) E334 ERROR ON PIPE IN-E TEMPERATURE SENSOR(SHORT OR OPEN) E335 ERROR ON PIPE OUT-A TEMPERATURE SENSOR(SHORT OR OPEN) E336 ERROR ON PIPE OUT-B TEMPERATURE SENSOR(SHORT OR OPEN) Samsung Electronics...
Page 49
ERROR DUE TO INPUT CURRENT SENSOR OF INVERTER PBA(SHORT/OPEN) E488 INCOMING VOLTAGE SENSOR ERROR E500 IPM/PFCM OVERHEAT ERROR E554 THE REFRIGERANT LEAKS COMPLETELY FROM THE OUTDOOR UNIT ERROR DUE TO INDOOR UNIT SOFTWARE VERSION COMBINATION(INCOMPATIBLE INDOOR E563 UNITSOFTWARE ON A SYSTEM) E590 INVERTER EEPROM CHECKSUM ERROR Samsung Electronics...
• At this point it is possible to start the internal units in the desired mode. ※ If " "doesn’t display, the procedure has failed and it is therefore necessary to read ALL the operator’s NOTE manual before repeating the operating described in steps 1-2-3-4. Samsung Electronics...
Page 51
Indication on the display and action to take when an inverter fault is detected. SEG1 SEG2 SEG3 SEG4 Action to take Fault detection is in progress PBA defect: Replace the PBA Check Manual inspection is required Going into fault detection mode failed Try fault detection again Samsung Electronics...
Page 52
Outdoor temperature EEV2 current step Running current EEV3 current step Target Discharge temperature EEV4 current step Total capacity of the indoor units Fan RPM (H: high, L: low, Blank: off ) Safety Control (just For Service Technician) 4-10 Samsung Electronics...
2 Press ❹ button to enter SEG8. Step 5 Press ❶ button to be changed to FAN mode in the ON status. 1 Press ❺ button to enter SEG9 value. 2 Press ❹ button to enter SEG10 value. 4-12 Samsung Electronics...
Page 55
1 Press ❺ button to enter SEG23 value. 2 Press ❹ button to enter SEG24 value. Step 12 Press ❶ button to check whether the option code you entered is correct or not. Press operation button to enter option. Samsung Electronics 4-13...
• If you set the SEG 9 as 0, the indoor unit will maintain previous RMC ADDRESS even if you input the option value of SEG11~12. 5 The MAIN address is for commnication between the indoor unit and the outdoor unit. Therefore, you must set it to operate the air conditioner properly 4-14 Samsung Electronics...
Disuse Use(Cooling) Use(Cooling) Reserved Reserved Disuse (Cooling/ Indication Heating) and Details (Cooling/ Heating) Use (Cooling Disuse Ultra low speed) Use (Cooling Ultra low speed) Use (Heating/ Disuse Cooling Ultra low speed)) Use (Heating/ Cooling Ultra low speed) Samsung Electronics 4-15...
Page 58
If external drain pump signal is used, external control (SEG14) can't be used. • 3) SEG20 If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1) 4-16 Samsung Electronics...
Page 60
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1) • 6) SEG21 Default value of Heating setting compensation is 9°F(5℃). 4-18 Samsung Electronics...
Page 62
Thermo on Use of buzzer hours Disuse Main, On/Off Existing control Reserved Window Indication On/Off and details Disuse Sub, On/Off Reverse control Window Operation Disuse of 2000 On/Off buzzer hours Disuse Main, On/Off Reverse control Window On/Off 4-20 Samsung Electronics...
Page 63
Soft Off: The indoor unit turns off its operation at the indicated time in the table for Installation Option after its final motion detection. But, it turns on again if the MDS detects motion. Hard Off: Designated time after SOFT OFF, it cannot turn on automatically when it detects motion. Users should control to turn on the indoor unit with remote control, etc. Samsung Electronics 4-21...
Page 64
RESERVED Indication and 2.7°F(1.5°C) 20 minutes Details 5.4°F(3°C) No delay 5.4°F(3°C) 10 minutes 5.4°F(3°C) 20 minutes 8.1°F(4.5°C) No delay 8.1°F(4.5°C) 10 minutes 8.1°F(4.5°C) 20 minutes (Heater 10.8°F(6°C) No delay time delay) 10.8°F(6°C) 10 minutes 10.8°F(6°C) 20 minutes 4-22 Samsung Electronics...
Page 65
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1) • 4) SEG21 Default value of Heating setting compensation is 3.6°F(2℃). Samsung Electronics 4-23...
Page 66
Use (Heating/Cooling Disuse Ultra low speed) Use (Heating/Cooling Ultra low speed) Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12 Function Page Use of drain pump Indication Details Indication Details Disuse Indication Reserved Reserved Reserved Reserved details external drain pump 4-24 Samsung Electronics...
Page 67
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1) • 6) SEG21 Default value of Heating setting compensation is 9°F(5°C). Samsung Electronics 4-25...
Page 68
Disuse Use(Heating) Use(Heating) Disuse Use(Cooling) Reserved Reserved Use(Cooling) Indication Disuse Use (Cooling/Heating) details Use (Cooling/Heating) Use (Cooling Ultra low Disuse speed) Use (Cooling Ultra low speed) Use (Heating/Cooling Disuse Ultra low speed) Use (Heating/Cooling Ultra low speed) 4-26 Samsung Electronics...
Page 69
No delay 2.7°F(1.5°C) Reserved minutes Indication 2.7°F(1.5°C) details minutes 5.4°F(3°C) No delay 5.4°F(3°C) minutes 5.4°F(3°C) minutes 8.1°F(4.5°C) No delay 8.1°F(4.5°C) minutes 8.1°F(4.5°C) minutes with 3 (Heater 10.8°F(6°C) No delay minute time delay delay) 10.8°F(6°C) minutes 10.8°F(6°C) minutes Samsung Electronics 4-27...
Page 70
If you set the Individual control with remote control option to a value other than 0 to 4, it is automatically set to 0 (Indoor 1) • 4) SEG21 Default value of Heating setting compensation is 3.6°F(2℃). 4-28 Samsung Electronics...
CAUTION If you set an indoor unit as the master indoor unit by using the remote control, the outdoor unit automatically operate in the current mode of the master indoor unit. Samsung Electronics 4-29...
The compressor stops intermittently or the fan speed of the COOL mode or DRY mode, and fan speed of the indoor unit decreases to prevent inside/outside air frozen indoor unit decreases. depending on the inside/outside air temperature. 4-34 Samsung Electronics 4-34...
Page 77
Troubleshooting ■ If Error code is displayed on indoor or outdoor LED, check as follows; Contents Turn on the system. But outdoor units PCB displayed E201 or E101 Error code. Check point Remarks Check point Remarks Check to power cable to indoor units. Step 1 Wire connect Check to communication cable indoor units.
Page 78
Troubleshooting - Address setting another case Contents When the system installation is finished, outdoor unit’s PCB display E202 Error code. Check point Remarks This problem is caused by outdoor unit’s communica- Analysis tion part trouble or indoor units power and communica- The pipe checking operation tion line trouble.
Page 79
Troubleshooting - Operation Error Contents While using cooling or heating, indoor units display E161 Error code. Check point Remarks This problem is caused by user’s fault. User’s simultaneously operate 2 more indoor units in the same time cool- Analysis ing and heating mode. FJM is operate by just cooling or heating mode only.
Page 80
Troubleshooting Contents While using heating, outdoor unit turn off and display E404 Error code. Check point Remarks Heating overload safety mode make this situation. Analysis After System restart automatically until 3 times, System display this error code and stop. System can operate by remote controller input signal or K3(reset) key input. Step 1 Check indoor units air flow.
Troubleshooting 4-5 Setting to Cool or Heat only mode, checking and Cool/Heat modes operation test Setting the outdoor option • Press and hold K2 to enter the option setting. (Only available when the operation is stopped) - If you enter the option setting, display will show the following. - Seg 1 and Seg 2 will display the number for selected option.
Page 82
This function enables the indoor units connected to the outdoor unit to operate in a specific mode. You can set each mode with Keys on the Main PCB in the outdoor unit. Set mode SEG1 SEG2 SEG3 SEG4 Cooling and Heating Only Cooling Only Heating • Default value: Cooling and Heating mode 4-40 Samsung Electronics...
In this case, is the resistance 8.300 value out of range in the temperature 10.00 table on the right? 12.10 Indoor temperature sensor 14.70 failure (replace) 18.00 Restart the system after 22.00 replacing the PCB 28.30 33.90 42.30 Samsung Electronics 4-41...
Page 84
PCB? Connect the connector to PCB and restart the unit. Is there foreign substance stuck in the motor fan? Remove the foreign substance and restart the unit. Replace the PCB and restart the unit. 4-42 Samsung Electronics...
Page 85
PCB and replace the PCB Reconnect the cable connecting the outdoor unit to the indoor unit and restart the unit. If the communication still doesn’t work, replace the indoor unit PCB. Good +0.7V -0.7V Samsung Electronics 4-43...
Page 86
EEPROM component failure, EEPROM circuit parts missing/damaged/soldering failure. Are the EEPROM circuit components in good conditions? (missing components / damage / soldering failure) Replace the PCB if the restart fails Restart the unit after replacing the PCB 4-44 Samsung Electronics...
2 (~) and 4 (~) of the bridge diode 220V? Is the fuse connected? Replace the fuse Replace the inverter PBA Is the resistance value of R001 200Ω? Is the reactor connector Connect the reactor. connected correctly? Replace the PBA. Samsung Electronics 4-45...
Main control 5V CE159 Voltage 4.75V - 5.25V 4. Checking PFCM Check Resistance between R and S AJ020BXJ2CH, AJ024BXJ3CH AJ***CXS*CH, AJ036BXJ4CH, AJ048BXJ5CH (INVERTER PBA) PFCM PFCM Measuring point Normal value Resistance R - S over the hundreds ㏀ 4-46 Samsung Electronics...
1V~6V? Replace inverter PCB. Is the fan running the operation mode? Does the voltage between pin6 and pin3 of the fan (CNP901 or CN901) Replace the fan motor. fluctuate? (High 5V~6V, Low:0V~1V) Replace the inverter PCB. Samsung Electronics 4-47...
Is the resistance value Replace the compressor. between the compressor boday and the chassis in the range of Mega Ω Is the compressor connection wire connected to the Check the connection wire. compressor correctly? Replace the outdoor unit Main PCB. 4-48 Samsung Electronics...
Trun off the power and reconnect the table. value normal? Does the voltage Trun off the power and correct or replace between pin6 and pin3 of the fan (CN901) fluctuate? the temperature sensor location. (High 5V~6V, Low:0V~1V) Replace the inverter PCB. Samsung Electronics 4-49...
40°C - 115kohm Connect the sensor to PBA connector supply power and measure the voltage of sensor in the connector. Exchange the Outdoor PBA. Below 0.5V or Over 4.5V? Micom error or connector check. Exchange the Outdoor PBA. Temperature[℃] 4-50 Samsung Electronics...
Page 93
40°C - 5.83kohm Connect the sensor to PBA connector supply power and measure the voltage of sensor in the connector. Below 0.5V or Over 4.5V? Exchange the Outdoor PBA. Micom error or connector check. Exchange the Outdoor PBA. Temperature[℃] Samsung Electronics 4-51...
The parts should be replaced in the following procedure. The repair is completed. Check the operation of the new part. Replace it with a new part. Detach the faulty part. Check for any faulty part. Set an address. 4-52 Samsung Electronics...
PCB Diagram 5. PCB Diagram 5-1 Indoor unit ■ Slim 1 Way, Mini 4Way ▶ This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 96
#1 : COM1(F1) #1 : L- LIVE POWER INPUT #1 : N-NEUTRAL POWER #2 : COM1(F2) OUTPUT #3 : V1(DC12V) #4 : V2(GND) #5 : COM2(F3) #6 : COM2(F4) This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 97
PCB Diagram ■ Slim 1Way (PANEL) ▶ This Document can not be used without Samsung’s authorization. ① CN401-DISPLAY #1: DC12V #2: LED_0 #3: LED_1 #4: LED_2 #5: LED_3 #6: LED_4 #7: - #8: REMOCON Signal Out #9 : PANEL SELECTION...
Page 98
PCB Diagram 1. CN101-DISPLAY #1 : 12V #2~6 : LED CONTROL SIGNAL This Document can not be used without Samsung’s authorization.
Page 99
#1: DC12V #2: LED_0 #3: LED_1 #4: LED_2 #5: LED_3 #6: LED_4 #7: - #8: REMOCON OUTPUT SIGNAL #9 : PANEL SELECTION #10: REMOCON INPUT SIGNAL #11: GND #12: DC5V #13: - This Document can not be used without Samsung’s authorization.
Page 100
PCB Diagram ■ Mini 4Way (PANEL) - This Document can not be used without Samsung’s authorization. 1. CN01-DISPLAY #1 : DC12V #2 : LED_Operation #3 : LED_Defrost #4 : LED_Timer #5 : - #6 : LED_Filter #7 : - #8 : Remocon Signal Out...
Page 101
PCB Diagram ■ Home Duct ▶ This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 102
#3~6 : FAN MOTOR SIGNAL CONTROL SIGNAL SIGNAL CONTROL SIGNAL #6 : DC 5V #3 : DC 12V #7~12 : COMMUNICATION #4 : GND SIGNAL #4~6 : COM2 COMMUNICATION SIGNAL This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 103
PCB Diagram ■ Duct S ▶ This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 104
#5 : DISCHARGE SENSOR #6 : GND 17. CN826-FAN MOTOR 18. SH100-EARTH #1 : MOTOR-U PHASE #1 : GND EARTH #2 : MOTOR-V PHASE #3 : MOTOR-W PHASE This Document can not be used without Samsung’s authorization. 5-10 Samsung Electronics...
Page 105
PCB Diagram ■ Console ▶ This Document can not be used without Samsung’s authorization. 11 16 19 18 14 4 13 5 12 15 6 Samsung Electronics 5-11...
Page 106
17. CN808-EEV 18. CN301-DOWNLOAD 19. CN201-EEPROM PBA CONNECTOR #1~#4:EEV CONTROL SIGNAL →For Developer only,Not available in #1:GND #5,#6:DC12V Actual Site #2:NOT USED →20 Pin Down Loader #3~#7:EEPROM SIGNAL This Document can not be used without Samsung’s authorization. 5-12 Samsung Electronics...
Page 107
PCB Diagram ■ MPAH ▶ This Document can not be used without Samsung’s authorization. Samsung Electronics 5-13...
Page 108
#1~2 : GND #1~2 : COM1 COMMUNICATION #1 : FLOAT SWITCH SIGNAL SIGNAL #2 : GND #3 : SPI CONTROL SIGNAL #3 : DC 12V #4 : NOT USED #4 : GND #4~6 : COM2 COMMUNICATION SIGNAL 5-14 Samsung Electronics...
PCB Diagram 5-2 Outdoor unit ■ AJ020BXJ2CH, AJ024BXJ3CH (INVERTER PBA) ▶ This Document can not be used without Samsung’s authorization. 1. CNP351-MAIN INV 2. CN030-MAIN POWER 3. CN571-ECO DOWNLOAD 4. CNP901-BLDC FAN #1 : RXD #1 : N #1 ~ 4 : ECO DOWNLOAD...
Page 110
PCB Diagram ■ AJ020BXJ2CH, AJ024BXJ3CH (MAIN PBA) ▶ This Document can not be used without Samsung’s authorization. 5-16 Samsung Electronics...
Page 111
#3 : EEV D SIGNAL #4 : EEV A SIGNAL #4 : EEV B SIGNAL #4 : EEV D SIGNAL #5 : GND #5 : GND #5 : GND This Document can not be used without Samsung’s authorization. Samsung Electronics 5-17...
Page 112
PCB Diagram ■ AJ***CXS*CH, AJ036BXJ4CH, AJ048BXJ5CH (INVERTER PBA) ▶ This Document can not be used without Samsung’s authorization. 1. L, N - AC POWER INPUT 2. REACTOR-A1/B1 3. REACTOR-A2/B2 4. CN551 - DOWNLOAD #1 : L - LIVE POWER INPUT /...
Page 113
PCB Diagram ■ AJ***CXS*CH, AJ036BXJ4CH, AJ048BXJ5CH (MAIN PBA) ▶ This Document can not be used without Samsung’s authorization. Samsung Electronics 5-19...
Page 114
#3 : GND #2 : - #4 : COMP CHECK #4 : DC 5V #3 : N - NEUTRAL POWER #5 : DC 12V OUTPUT #6 : INV POWER CTRL This Document can not be used without Samsung’s authorization. 5-20 Samsung Electronics...
Page 115
PCB Diagram ■ AJ***CXS*CH, AJ036BXJ4CH, AJ048BXJ5CH (EMI PBA) - This Document can not be used without Samsung’s authorization. 1. L1 - AC POWER OUTPUT 2. L2 - AC POWER OUTPUT 3. CN01 - AC POWER OUTPUT 4. EARTH #1 : L - RELAY CONTACT...
F) at 200k Ω ° ° ※OPTION L1 L2 L1 L2 L1 L2 AC POWER INDOOR-UNIT INDOOR-UNIT USE COPPER SUPPLY WIRES. INPUT POWER COMM UTILISER DES FILS D'ALIMENTATION EN CUIVRE. This Document can not be used without Samsung’s authorization. Samsung Electronics...
Page 122
■ AJ***CXS*CH, AJ036BXJ4CH, AJ048BXJ5CH This Document can not be used without Samsung’s authorization. Samsung Electronics...
Contact CAUTION your dealer for advice. • Minimum installation height of indoor unit is 0.6 m for floor mounted, 1.8 m for wall, 2.2 m for ceiling. Samsung Electronics...
2. Make sure that you put the remote control unit in an area not exposed to direct sunlight, and where there is no source of heat. 3. Make sure that you use the remote control unit in an area away from TVs, audio units, cordlessphones, fluorescent lighting. Samsung Electronics...
(N · m) port cap (Refer to the table) ø 6.35 20 to 25 ø 9.52 20 to 25 10 to 12 ø 12.70 25 to 30 R-140A : Diameter of the screw-1/2-20UNF ø 15.88 30 to 35 Samsung Electronics...
7) Stop operation of the air conditioner. AJ034NCJ5CH, AJ038NCJ5CH 8) Close the 3 way valve, disconnect the pres- sure gauge, and open the 3 way valve again. 9) Close the cap of each valve. Samsung Electronics...
Tightening torque Outer diameter (mm) Body cap (N · m) Charging port cap (N · m) ø 6.35 20 to 25 ø 9.52 20 to 25 10 to 12 ø 12.70 25 to 30 ø 15.88 30 to 35 Samsung Electronics...
6. Make sure you do not bend the connection pipes in the middle and store together with the cables. 7. Move the indoor and outdoor units to a new location. 8. Remove the mountin g plate for the indoor unit and move it to a new location. Samsung Electronics...
2016 Europe 2017 (6) Design 2018 Wind-Free, GEO 2019 Wind-Free, AIRISE 2020 2021 AIRISE 2022 2023 (4) Inverter type (7) Series HP, R410A 1st Model HP, R32 2nd Model 7/15K FJM Only Wind-Free Mass North America PM1.0 Wind-Free Samsung Electronics...
Page 130
220~240V, 50/60Hz 2023 200~220V, 50Hz 208~230V, 60Hz, 3Φ 220~240V, 50Hz 127V, 50Hz (4) Inverter type 208~230V, 60Hz, 3Φ 380~415, 50/60Hz, 3Φ Indoor unit (NASA) 380~415V, 50Hz, 3Φ Outdoor unit (NASA) Indoor unit (Non NASA) Outdoor unit (Non NASA) Samsung Electronics...
Page 131
2021 200~220V, 50Hz 208~230V, 60Hz, 3Φ 2022 220~240V, 50Hz 127V, 50Hz 2023 208~230V, 60Hz, 3Φ 380~415, 50/60Hz, 3Φ 380~415V, 50Hz, 3Φ (4) Product type Indoor unit (NASA) Outdoor unit (NASA) Indoor unit (Non NASA) Outdoor unit (Non NASA) Samsung Electronics...
(T_O1) Compressor (Comp) ROOM A Service Valve - Gas Pipe1 (SV_G1) Thermistor - Out 2 (T_O2) ROOM B Service Valve - Gas Pipe2 (SV_G2) Thermistor - Out 3 (T_O3) ROOM C Service Valve - Gas Pipe3 (SV_G3) 7-10 Samsung Electronics...
Page 133
ROOM C Service Valve (AC) - Gas Pipe3 (SV_G3) Thermistor - Out 4 (T_O4) Compressor ROOM D Service Valve (Comp) Thermistor - Out 5 - Gas Pipe3 (SV_G4) (T_O5) ROOM E Service Valve - Gas Pipe3 (SV_G5) Samsung Electronics 7-11...
Page 134
ROOM B Service Valve Thermistor - Out 3 - Gas Pipe2 (SV_G2) (T_O3) Accmulator ROOM C Service Valve (AC) Thermistor - Out 4 - Gas Pipe3 (SV_G3) (T_O4) Compressor ROOM D Service Valve (Comp) - Gas Pipe3 (SV_G4) 7-12 Samsung Electronics...
Page 135
ROOM B Service Valve Thermistor - Out 3 - Gas Pipe2 (SV_G2) (T_O3) Accmulator ROOM C Service Valve (AC) Thermistor - Out 4 - Gas Pipe3 (SV_G3) (T_O4) Compressor ROOM D Service Valve (Comp) - Gas Pipe3 (SV_G4) Samsung Electronics 7-13...
(Full name : Heat exchanger; A device, used to transfer heat from a fluid on one side of a barrier assemble evaporator / to a fluid on the other side without bringing the fluids into direct contact. assemble condenser) 7-14 Samsung Electronics...
Samsung Electronics do not manufacture drain pumps. So, we are not able to correct the drain pump problems. Whenever the air conditioner is turned on, it irritates my eyes and gives me a headache.
Page 138
Also, the remote controller may not work under intensive light from a 3-wave length lamp or a neon sign due to the EMI. In this case, take the remote controller closer to the receiver. 7-16 Samsung Electronics...
Page 139
There is a cost table. But, our service engineer needs to visit to total up the cost correctly. When you move in, make sure to contact Samsung Electronics Service Center or Authorized Service Agent in advance to streamline the process.
But generally the value of fresh indoor temperature is that below 0.2(m/s) of indoor air circulation, the temperature is 21~28°C when the wall temperature is the same as the indoor's and relative humidity is 30~31% in summer, the winter temperature is 20~24°C and relative humidity is 30~60% in winter. 7-18 Samsung Electronics...