Toshiba MMW-AP0481CHQ-E Service Manual page 94

Hot water module high temperature type
Hide thumbs Also See for MMW-AP0481CHQ-E:
Table of Contents

Advertisement

Procedure 1: reading setting data from EEPROM
(Read the setting data from EEPROM, including both the factory settings and any modifications made to them
on site.)
1
Push the
+
* In the case of group control, the unit No. displayed first is the indoor unit (including Hot Water Module)
No. of the header unit.
At the same time, the CODE No. (DN code)
2
Each time the
UNIT LOUVER
No. under group control is displayed in turn.
3
The
button allows you to move the CODE No. (DN code) up / down by one place.
4
First, change the CODE No. (DN code) from
Jot down the setting data displayed.
5
Change the CODE No. (DN code) using the
Again, jot down the setting data displayed.
6
Repeat step 5 until all the setting data has been jotted down. (See the CODE No. list.)
* CODE No. (DN code) go from
7
When finished, push the
(It takes the system about 1 minute to become responsive to remote controller operation.)
CODE No. (DN code) necessary at minimum
DN
Contents
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor address
14
Group address
+
buttons simultaneously and hold for at least 4 seconds.
button (left side of the button) is pushed, one of the Hot Water Module
01
FF
to
with a few gaps along the way.
button to bring the system back to normal off state.
Remote controller operation diagram
10
is displayed.
10 10 10 10 10
03 03 03 03 03
to
. (To set central control address)
button.
– 94 –