Toshiba MMW-AP0481CHQ-E Service Manual page 52

Hot water module high temperature type
Hide thumbs Also See for MMW-AP0481CHQ-E:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
A27
A28
E01
E02
E03
E04
No. of indoor units from
which signal is received
normally
E06
E06
E07
Duplicated indoor
address
E08
E08
E09
Location
Description
of
detection
Indoor unit
High-pressure
(H-HWM)
protective
operation
Indoor unit
H-HWM
(H-HWM)
communication
trouble between
I/F and IPDU.
Remote
Indoor-remote
controller
controller
communication
trouble
(detected at
remote
controller end)
Remote
Remote
controller
controller
transmission
trouble
Indoor unit
Indoor-remote
controller
communication
trouble
(detected at
indoor end)
Indoor unit
Indoor-outdoor
communication
circuit trouble
(detected at
indoor end)
I/F
Signal lack of
indoor unit
I/F
Indoor-outdoor
communication
circuit trouble
(detected at
outdoor end)
Indoor unit I/F
Duplicated
indoor address
Remote
Duplicated
controller
master remote
controller
Check code detection
System status
condition(s)
Stop of
PD sensor detect
corresponding
pressuere is higher than
unit
the specified value.
Stop of
Communication
corresponding
interrupted between
unit
H-HWM P.C. board (I/F)
and H-HWM P.C. board
(IPDU).
Stop of
Communication between
corresponding
indoor P.C. board and
unit
remote controller is
disrupted.
Stop of
Signal cannot be
corresponding
transmitted from remote
unit
controller to indoor unit.
Stop of
There is no
corresponding
communication from
unit
remote controller
Stop of
Indoor unit is not
corresponding
receiving signal from
unit
outdoor unit.
All stop
Indoor unit initially
communicating normally
fails to return signal for
specified length of time.
All stop
Signal cannot be
transmitted from outdoor
to indoor units for 30
seconds continuously.
All stop
More than one indoor
unit are assigned same
address.
Stop of
In two remote controller
corresponding
configuration both
unit
controllers are set up as
master.
(Header indoor unit is
shut down with alarm,
while follower indoor
units continue operating.)
– 52 –
Check items (locations)
• Check PD pressure sensor trouble.
• Check clogging of PMV 2.
• Check clogging of heat exchangers.
• Check H-HWM P.C. board (I/F)
trouble.
• Check refrigerant overcharge
(R134a).
• Check H-HWM P.C. board (I/F)
trouble.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check remote controller inter-unit
tie cable (A/B).
• Check for broken wire or connector
bad contact.
• Check indoor power supply.
• Check for trouble in indoor P.C.
board.
• Check remote controller address
settings (when two remote
controllers are in use).
• Check remote controller P.C. board.
• Check internal transmission
circuit of remote controller.
--- Replace remote controller as
necessary.
• Check remote controller wiring.
• Check order in which power was
turned on for indoor and outdoor
units.
• Check indoor address setting.
• Check indoor-outdoor wiring.
• Check outdoor terminator resistor
setting (SW30, Bit 2).
• Check power supply to indoor unit.
(Is power turned on?)
• Check connection of indoor-
outdoor communication cable.
• Check connection of
communication connectors on
indoor P.C. board.
• Check connection of
communication connectors on
outdoor P.C. board.
• Check for trouble in indoor P.C.
board.
• Check for trouble in outdoor P.C.
board (I/F).
• Check outdoor terminator resistor
setting (SW30, Bit 2).
• Check connection of indoor-
outdoor communication circuit.
• Check indoor addresses.
• Check for any change made to
remote controller connection
(group/ individual) since indoor
address setting.
• Check remote controller settings.
• Check remote controller P.C. boards.