Toshiba MMW-AP0481CHQ-E Service Manual page 55

Hot water module high temperature type
Hide thumbs Also See for MMW-AP0481CHQ-E:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
01: TS1 sersor trouble
02: TS2 sersor trouble
F12
F12
01: TS1 sersor trouble
02: TS2 sersor trouble
F13
F13
F15
F15
F16
F16
F23
F23
F24
F24
F29
F31
F31
*1 Total shutdown in case of header unit
Continued operation in case of follower unit
Location
Description
of
detection
I/F
TS1/TS2 sensor
trouble
IPDU
TH sensor trouble All stop
I/F
Outdoor
temperature
sensor wiring
trouble (TE1, TL1)
I/F
Outdoor pressure
sensor wiring
trouble (PD, PS)
I/F
PS sensor
trouble
I/F
PD sensor
trouble
Indoor unit
Other indoor
trouble
I/F
Outdoor
EEPROM trouble
Check code detection
System status
condition(s)
All stop
Sensor resistance is
infinity or zero (open/
short circuit).
Sensor resistance is
infinity or zero (open/
short circuit).
All stop
During compressor
operation in HEAT mode,
TL1 continuously
provides temperature
reading higher than
indicated by TL1 by at
least specified margin for
3 minutes or more.
All stop
Readings of high-
pressure PD sensor and
low-pressure PS sensor
are switched.
Output voltages of both
sensors are zero.
All stop
Output voltage of PS
sensor is zero.
All stop
Output voltage of PD
sensor is zero (sensor
open-circuited).
Pd > 4.15MPa despite
compressor having been
turned off.
Stop of
Indoor P.C. board does
corresponding
not operate normally.
unit
All stop *1
Outdoor P.C. board (I/F)
does not operate
normally.
– 55 –
Check items (locations)
• Check connection of TS1/TS2
sensor connector
• Check resistance characteristics
of TS1/TS2 sensor.
• Check for trouble in indoor P.C.
board.
• Trouble in IPM built-in temperature
sensor
→ Replace A3-IPDU P.C. board.
• Check installation of TE1 and TL1
sensors.
• Check resistance characteristics
of TE1 and TL1 sensors.
• Check for outdoor P.C. board (I/F)
trouble.
• Check connection of high-pressure
PD sensor connector.
• Check connection of low-pressure
PS sensor connector.
• Check for defect in pressure
sensors PD and PS.
• Check for trouble in outdoor P.C.
board (I/F).
• Check for deficiency in
compressive output of compressor.
• Check for connection trouble
involving PS sensor and PD
sensor connectors.
• Check connection of PS sensor
connector.
• Check for defect in PS sensor.
• Check for deficiency in
compressive output of compressor.
• Check for trouble in 4-way valve.
• Check for trouble in outdoor P.C.
board (I/F).
• Check for trouble in SV4 circuit.
• Check connection of PD sensor
connector.
• Check for trouble in PD sensor.
• Check for trouble in outdoor P.C.
board (I/F).
• Check for trouble in indoor P.C.
board (trouble EEPROM)
• Check power supply voltage.
• Check power supply noise.
• Check for trouble in outdoor P.C.
board (I/F).