Toshiba MMW-AP0481CHQ-E Service Manual page 51

Hot water module high temperature type
Hide thumbs Also See for MMW-AP0481CHQ-E:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
A14
A15
A16
A17
A18
A19
A21
A22
A23
A24
A25
A26
Location
Description
of
detection
Indoor unit
Heat sink
(H-HWM)
overheat trouble
Indoor unit
IGBT short-circuit
(H-HWM)
protection trouble
Indoor unit
Current detection
(H-HWM)
circuit system
trouble
Indoor unit
Compressor
(H-HWM)
trouble (lock)
Indoor unit
Compressor
(H-HWM)
breakdown
Indoor unit
Compressor
(H-HWM)
position detection
circuit system
trouble
Indoor unit
Inverter DC
(H-HWM)
voltage (Vdc)
trouble
(compressor)
Indoor unit
Compressor case
(H-HWM)
thermostat
operation
Indoor unit
High-pressure
(H-HWM)
SW system
trouble
Indoor unit
TH sensor trouble Stop of
(H-HWM)
Indoor unit
Discharge
(H-HWM)
temperature TD
trouble
Indoor unit
Gas leak
(H-HWM)
detection (R134a)
Check code detection
System status
condition(s)
Stop of
IGBT built-in temp sensor
corresponding
(TH) is overheated.
unit
Stop of
Instant over-current was
corresponding
detected when
unit
compressor started
operation.
Stop of
While inverter
corresponding
compressor stopped, the
unit
status that current flowed
more than the specified
amount was detected
Stop of
Over-current was
corresponding
detected a few seconds
unit
after inverter compressor
had started.
Stop of
Inverter current detection
corresponding
circuit detected over-
unit
current and stopped.
Stop of
Position detection is not
corresponding
going on normally.
unit
Stop of
Inverter DC voltage is too
corresponding
high (overvoltage) or too
unit
low (undervoltage).
Stop of
Compressor case
corresponding
thermostat performed
unit
protective operation due
to overheating of
compressor.
Stop of
High-pressure SW
corresponding
operated.
unit
Resistance value of
corresponding
sensor is infinite or zero
unit
(Open/Short circuit).
Stop of
Discharge temperature
corresponding
(TD) is higher than the
unit
specified value.
Stop of
Discharge temperature
corresponding
(TD) and refrigerant
unit
superheat (SH) are
highger than the
specified value.
– 51 –
Check items (locations)
• Check power voltage
• Check cooling fan trouble.
• Check clogging of heat sink
cooling duct.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check connection of cabling
connector on H-HWM P.C. board
(IPDU).
• Check compressor trouble and
layer short circuit.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check compressor trouble
• Check power voltage.
(AC220V - 10% to 240V + 10%).
• Check cable of compressor system
and phase-missing.
• Check connector/terminal
connection on H-HWM P.C. board
(IPDU).
• Check H-HWM P.C. board (IPDU)
trouble.
• Check power voltage
(AC220V - 10% to 240V + 10%).
• Check compressor trouble.
• Check cause of abnormal overload
operation.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check connection of cabling
connector
• Check compressor trouble and
layer short circuit.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check TD sensor trouble
• Check clogging of PMV 2.
• Check clogging of cascade heat
exchanger.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check refrigerant shortage (R134a)
• Check PD pressure sensor trouble
• Check clogging of PMV2.
• Check clogging of water heat
exchanger.
• Check H-HWM P.C. board (IPDU)
trouble.
• Check refrigerant overcharge
(R134a)
• Check H-HWM P.C. board (IPDU)
trouble.
• Check clogging of PMV2.
• Check characteristics of TD sensor
resistance value.
• Check refrigerant shortage
(R134a).
• Check refrigerant shortage (R134a).
• Check clogging of PMV2.
• Check characteristics of TD sensor
resistance value.

Advertisement