Hot water module high temperature type
Hide thumbs Also See for MMW-AP0481CHQ-E:
Table of Contents

Advertisement

Check code
Outdoor 7-segment display
Main
remote
Check
controller
Sub-code
code
01: Compressor 1 side
02: Compressor 2 side
P26
P26
01: Compressor 1 side
02: Compressor 2 side
P29
P29
P31
Location
Description
of
detection
IPDU
IPM shortcircuit
protection trouble
IPDU
Compressor
position detection
circuit trouble
Indoor unit
Other indoor
trouble
(group follower
unit trouble)
Check code detection
System status
condition(s)
All stop
Overcurrent is
momentarily detected
during startup of
compressor.
All stop
Position detection is not
going on normally.
Stop of
There is trouble in other
corresponding
indoor unit in group,
unit
resulting in detection of
E07/L07/L03/L08.
– 64 –
Check items (locations)
• Check connector connection and
wiring on A3-IPDU P.C. board.
• Check for trouble in compressor
(layer shortcircuit).
• Check for trouble in outdoor P.C.
board (A3-IPDU).
• Check wiring and connector
connection.
• Check for compressor layer short-
circuit.
• Check for trouble in A3-IPDU P.C.
board.
• Check indoor P.C. board.