Toshiba MMW-AP0481CHQ-E Service Manual page 109

Hot water module high temperature type
Hide thumbs Also See for MMW-AP0481CHQ-E:
Table of Contents

Advertisement

No.
Part to be replaced
16
Pressure sensor
(PD, PS)
Work procedure
1. Detachment
1) Carry out the detachment of item 1 .
2) Remove the connectors from I/F P.C. board.
CN606 ...PD (3 P : Black)
CN605 ...PS (3 P : Yellow)
3) Remove the cap for check joint and attach the
pressure sensor by two wrenches with the
tightening torque of 12+2 N m.
4) Fix the PD and PS sensor with the binding band
as shown in figure.
NOTE:
• Attach the capillary tubes for PD or PS sensor so
that they do not touch the ceiling board or front
panel.
2. Attachment
1) Carry out installation by following the detachment
procedure in reverse.
Fix the PD and PS sensor so that upper surface of the
PD and PS sensor is lower than that of electric parts box.
Fix the PD and PS sensor with binding band.
(Two places)
– 109 –
Remarks
Check joint
PD sensor
PS sensor
PD sensor
Wrench
Take space 20 mm or more.
Front panel
PS sensor
PD sensor
Take space 20
mm or more.