SERVICE MANUAL

AIR-CONDITIONER
INDOOR UNIT
<Ceiling type>
MMC-AP0157HP-E (TR)
MMC-AP0187HP-E (TR)
MMC-AP0247HP-E (TR)
MMC-AP0277HP-E (TR)
MMC-AP0367HP-E (TR)
MMC-AP0487HP-E (TR)
MMC-AP0567HP-E (TR)
SVM-13085.indb 1
SVM-13085.indb 1
(MULTI TYPE)
FILE NO. SVM-13085
12/24/13 10:56 AM
12/24/13 10:56 AM

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MMC-AP0157HP-E (TR)

  • Page 1: Service Manual

    FILE NO. SVM-13085 SERVICE MANUAL AIR-CONDITIONER (MULTI TYPE) INDOOR UNIT <Ceiling type> MMC-AP0157HP-E (TR) MMC-AP0187HP-E (TR) MMC-AP0247HP-E (TR) MMC-AP0277HP-E (TR) MMC-AP0367HP-E (TR) MMC-AP0487HP-E (TR) MMC-AP0567HP-E (TR) SVM-13085.indb 1 SVM-13085.indb 1 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 2: Table Of Contents

    FILE NO. SVM-13085 Original instruction Adoption of R410A Refrigerant This Air Conditioner adopted refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. CONTENTS SAFETY CAUTION ........3 1. CONSTRUCTION VIEWS (EXTERNAL VIEWS) ......15 1-1.
  • Page 3: Safety Caution

    The qualified service person is a person who installs, repairs, maintains, relocates and removes the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install, repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation...
  • Page 4 FILE NO. SVM-13085 Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
  • Page 5: Warning Indications On The Air Conditioner Unit

    FILE NO. SVM-13085 Warning Indications on the Air Conditioner Unit [Confirmation of warning label on the main unit] Confirm that labels are indicated on the specified positions If removing the label during parts replace, stick it as the original. WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD...
  • Page 6: Precaution For Safety

    FILE NO. SVM-13085 Precaution for Safety The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. DANGER Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit breaker to the OFF position.
  • Page 7 FILE NO. SVM-13085 Electrical wiring work shall be conducted according to law and regulation in the community and Installation manual. Failure to do so may result in electrocution or short circuit. To connect the electrical wires, repair the electrical parts or undertake other electrical jobs, wear gloves to provide protection for electricians, insulating shoes and clothing to provide protection from electric shocks.
  • Page 8 FILE NO. SVM-13085 Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then apply a water-cut method, otherwise a leak or production of fire is caused at the users' side. Insulating measures When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because the oil that coats the pipes may otherwise burn.
  • Page 9 FILE NO. SVM-13085 When the refrigerant gas leaks, find up the leaked position and repair it surely. If the leaked position cannot be found up and the repair work is interrupted, pump-down and tighten the service valve, otherwise the refrigerant gas may leak into the room. The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.
  • Page 10 FILE NO. SVM-13085 Only a qualified installer or service person is allowed to do installation work. Inappropriate installation may result in water leakage, electric shock or fire. Before starting to install the air conditioner, read carefully through the Installation Manual, and follow its instructions to install the air conditioner.
  • Page 11: Declaration Of Conformity

    FILE NO. SVM-13085 Declaration of Conformity Manufacturer: TOSHIBA CARRIER (THAILAND) CO., LTD. 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Amphur Muang, Pathumthani 12000, Thailand Authorized Nick Ball Representative/TCF holder: Toshiba EMEA Engineering Director Toshiba Carrier UK Ltd.
  • Page 12 FILE NO. SVM-13085 Specifications Sound power level (dBA) Model Weight (kg) Cooling Heating MMC-AP0157HP-E ∗ ∗ MMC-AP0187HP-E ∗ ∗ MMC-AP0247HP-E ∗ ∗ MMC-AP0277HP-E ∗ ∗ MMC-AP0367HP-E ∗ ∗ MMC-AP0487HP-E ∗ ∗ MMC-AP0567HP-E ∗ ∗ MMC-AP0157HP-TR ∗ ∗ MMC-AP0187HP-TR ∗ ∗ MMC-AP0247HP-TR ∗...
  • Page 13: R410A Refrigerant

    FILE NO. SVM-13085 • R410A Refrigerant This air conditioner adopted HFC type refrigerant (R410A) which does not deplete the ozone layer. 1. Safety Caution Concerned to R410A Refrigerant The pressure of R410A is high 1.6 times of that of the former refrigerant (R22). Accompanied with change of refrigerant, the refrigerating oil has been also changed.
  • Page 14 FILE NO. SVM-13085 4. Tools 1. Required Tools for R410A Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types. 1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22)) 2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22) 3) Tools commonly used for R410A and for conventional refrigerant (R22)
  • Page 15: Construction Views (External Views)

    FILE NO. SVM-13085 1. CONSTRUCTION VIEWS (EXTERNAL VIEWS) 1-1. Indoor Unit MMC-AP0157HP , AP0187HP – 15 – SVM-13085.indb 15 SVM-13085.indb 15 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 16: Mmc-Ap0247Hp * , Ap0277Hp

    FILE NO. SVM-13085 MMC-AP0247HP , AP0277HP – 16 – SVM-13085.indb 16 SVM-13085.indb 16 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 17: Mmc-Ap0367Hp * , Ap0567Hp

    FILE NO. SVM-13085 MMC-AP0367HP to AP0567HP – 17 – SVM-13085.indb 17 SVM-13085.indb 17 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 18: Wiring Diagram

    FILE NO. SVM-13085 2. WIRING DIAGRAM – 18 – SVM-13085.indb 18 SVM-13085.indb 18 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 19: Parts Rating

    FILE NO. SVM-13085 3. PARTS RATING MMC-AP***7HP* Parts name Model Specifi cations   ICF-340WD94-1   Fan motor ICF-340WD94-2    ICF-340WD139-1        Louver motor MP24Z3T       ...
  • Page 20: Refrigeration Cycle Diagram

    FILE NO. SVM-13085 4. REFRIGERATION CYCLE DIAGRAM Liquid side Gas side Strainer Capillary tubes Heat exchanger at indoor side Pulse Motor Valve (PMV) Strainer Sensor (TCJ) Sensor (TC2) Sensor (TC1) Sensor Fan motor (TA) Functional part name Functional outline Pulse Motor Valve (Connector CN82 (6P): Blue) 1) Controls super heat in cooling operation 2) Controls under cool in heating operation...
  • Page 21: Control Outline

    FILE NO. SVM-13085 5. CONTROL OUTLINE 5-1. Control Specifications Item Outline of specifications Remarks When power 1) Distinction of outdoor unit supply is reset When the power supply is reset, the outdoors are distinguished and the control is selected according to the distinguished result.
  • Page 22 FILE NO. SVM-13085 Item Outline of specifications Remarks Room temp. 2) Using the CODE N . 06, the setup temperature in heating Shift of suction control operation can be corrected. temperature in heating (Continued) operation Setup data Setup temp. correction +0°C +2°C +4°C...
  • Page 23 FILE NO. SVM-13085 Item Outline of specifications Remarks Air speed 1) Operation with (HH), (H), (L) or [AUTO] mode is carried HH > H+ > H > L+ > L > UL selection out by the command from the remote controller. 2) When the air speed mode [AUTO] is selected, the air speed varies by the difference between Ta and Ts.
  • Page 24 FILE NO. SVM-13085 Item Outline of specifications Remarks Air speed selection Selection of high ceiling type CODE No. : (Continued): [5d] or selection of high ceiling on P .C. board SW501 Standard Type 1 Type 3 CODE No. [5d] 0000 0001 0003 SW501 (1)/(2)
  • Page 25 FILE NO. SVM-13085 Item Outline of specifications Remarks Freeze prevention 1. In all cooling operation, the air conditioner operates TC1: Temperature of indoor control (Low temp. as described below based upon temp. detected by heat exchanger sensor release) TC1, TC2 and TCJ sensors. When “J”...
  • Page 26 FILE NO. SVM-13085 Item Outline of specifications Remarks Recovery control The indoor unit which is under STOP/Thermo. OFF The indoor unit which is for heating status or which operates in [FAN] mode performs the under thermo. OFF (COOL) refrigerant (Oil) following controls when it received the heating status or which operates in refrigerant (Oil) recovery signal from the outdoor unit.
  • Page 27 FILE NO. SVM-13085 Item Outline of specifications Remarks Display of < READY> Displayed on the remote controller < READY> display [READY] 1) When the following check codes are indicated No display for wireless [HEAT READY] type remote controller Open phase of power supply wiring [P05] was detected. There is an indoor unit that detected the indoor overflow [P10].
  • Page 28 FILE NO. SVM-13085 Item Outline of specifications Remarks Louver control: 1) Louver position setup When the louver position is changed, the position moves necessarily to downward discharge position once to return to the set position. The louver position can be set up in the following operation range.
  • Page 29 FILE NO. SVM-13085 Item Outline of specifications Remarks DC motor 1) DC motor operates according to the command from Check code [P12] the indoor controller. (Note) If the fan rotates by entry of outside air, etc while the air conditioner stopped, the indoor unit may operate as the fan motor stops.
  • Page 30: Configuration Of Control Circuit

    FILE NO. SVM-13085 6. CONFIGURATION OF CONTROL CIRCUIT 6-1. Indoor Unit 6-1-1. Indoor Controoler Block Diagram 1. Connection of wired remote controller Wired (Simple) header remote controller (Up to 2 units) Schedule timer Display LCD Function setup Display driver Key switch Display LED Function setup DC5V...
  • Page 31 FILE NO. SVM-13085 2. Connection of wired remote controller kit Indoor unit #1 (Header) Wireless remote (Follower) (Follower) controller kit Indoor control P.C. board Receiving (MCC-1643) P.C. board DC20V Remote controller Remote controller communication circuit communication circuit Emergent Power operation EEPROM circuit DC5V...
  • Page 32 FILE NO. SVM-13085 3. Connection of both wired remote controller and wireless remote controller kit Schedule timer Wired (Simple) header remote controller Display LCD Function setup Display driver Key switch EEPROM Function setup DC5V DC5V Power Display LED Key switch circuit Remote controller Secondary...
  • Page 33 FILE NO. SVM-13085 6-2. Indoor P.C. board MCC-1643 – 33 – SVM-13085.indb 33 SVM-13085.indb 33 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 34 FILE NO. SVM-13085 6-3. Functions at test run Cooling/Heating test run check The test run for cooling/heating can be performed from either indoor remote controller or outdoor interface P .C. board. 1. Start/Finish operation of test run Test run from indoor remote controller Wired remote controller: Refer to the below item of “Test run”...
  • Page 35 FILE NO. SVM-13085 In case of wireless remote controller 1. When TEMPORARY button is pushed for 10 seconds or more, “Pi!” sound is heard and the operation changes to a forced cooling operation. After approx. 3 minutes, a cooling operation starts forcedly. Check cool air starts blowing.
  • Page 36 FILE NO. SVM-13085 Check function for operation of indoor unit (Functions at indoor unit side) This function is provided to check the operation of the indoor unit singly without communication with the remote controller or the outdoor unit. This function can be used regardless of operation or stop of the system. However, if using this function for a long time, a trouble of the equipment may be caused.
  • Page 37 FILE NO. SVM-13085 6-4. Optional Connector Specifications of Indoor P.C. Board – 37 – SVM-13085.indb 37 SVM-13085.indb 37 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 38: Applied Control

    FILE NO. SVM-13085 7. APPLIED CONTROL 7-1. Setup of Selecting Function in Indoor Unit (Be Sure to Execute Setup by a Wired Remote Controller) <Procedure> Execute the setup operation while the unit stops. TEMP. ON / OFF TIMER SET MODE TIME SAVE VENT...
  • Page 39 FILE NO. SVM-13085 Table: Function selecting CODE No. (DN) (Items necessary to perform the applied control at the local site are described.) Item Description At shipment Filter display delay timer 0000 : None 0001 : 150H 0002 : 2500H 0002 : 2500H 0003 : 5000H 0004 : 10000H Dirty state of filter...
  • Page 40 FILE NO. SVM-13085 Item Description At shipment High ceiling selection AP015 to AP036 to 0000: Standard Model MMC- (Selection of air volume) AP027 AP056 DATA Standard Up to 3.5 m Up to 3.5 m 0000 (Factory default) High ceiling (1) Up to 4.0 m Up to 4.3 m 0003...
  • Page 41 FILE NO. SVM-13085 7-2. Applied Control in Indoor Unit Remote location ON/OFF control box (TCB-IFCB-4E2) [Wiring and setup] Use the exclusive connector for connection with the indoor control P.C. board. In a group control, the system can operate when connecting with any indoor unit (Control P.C. board) in the group.
  • Page 42 FILE NO. SVM-13085 Ventilating fan control from remote controller [Function] The start/stop operation can be operated from the wired remote controller when air to air heat exchanger or ventilating fan is installed in the system. The fan can be operated even if the indoor unit is not operating. Use a fan which can receive the no-voltage A contact as an outside input signal.
  • Page 43 FILE NO. SVM-13085 Leaving-ON prevention control [Function] This function controls the indoor units individually. It is connected with cable to the control P.C. board of the indoor unit. In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the CODE No. 2E is set to the connected indoor unit.
  • Page 44 FILE NO. SVM-13085 Address setup (Manual setting from remote controller) In case that addresses of the indoor units will be determined prior to piping work after cabling work (Example of 2-lines cabling) (Real line: Cabling, Broken line: Refrigerant pipe) Set an indoor unit per a remote controller. Outdoor Outdoor Turn on power supply.
  • Page 45 FILE NO. SVM-13085 Confirmation of indoor unit No. position 1. To know the indoor unit addresses though position of the indoor unit is recognized In case of individual operation (Wired remote controller : indoor unit = 1 : 1) (Follow to the procedure during operation) <Procedure>...
  • Page 46 FILE NO. SVM-13085 How to check all the unit No. from an arbitrary wired remote controller <Procedure> Carry out this procedure during stop of system. The indoor unit No. and the position in the identical refrigerant piping can be checked. An outdoor unit is selected, the identical refrigerant piping and the indoor unit No.
  • Page 47 FILE NO. SVM-13085 Changing the indoor unit address using a remote controller To change an indoor unit address using a wired remote controller. The method to change the address of an individual indoor unit (the indoor unit is paired with a wired remote controller one-to-one), or an indoor unit in a group. (The method is available when the addresses have already been set automatically.) TEMP.
  • Page 48 FILE NO. SVM-13085 How to change all indoor addresses from an arbitrary wired remote controller (It is possible when setting has finished by automatic addresses.) Contents: The indoor unit addresses in each identical refrigerant piping line can be changed from an arbitrary wired remote controller.
  • Page 49 FILE NO. SVM-13085 Function to clear error 1. Clearing method from remote controller How to clear error of outdoor unit In the unit of refrigerant line connected by indoor unit of the remote controller to be operated, the error of the outdoor unit currently detected is cleared.
  • Page 50 FILE NO. SVM-13085 Monitoring function of remote controller switch When using the remote controller (Model Name: RBC-AMT32E), the following monitoring function can be utilized. Calling of display <Contents> The temperature of each sensor of the remote controller, indoor unit and outdoor unit and the operating status can be checked by calling the service monitor mode from the remote controller.
  • Page 51 FILE NO. SVM-13085 Target outdoor unit (SMMS, SHRM, Mini-SMMS – Series 1 – 2) CODE No. Data Format Unit Remote controller display example Indoor unit Room temperature (in control) *1 ˚C data Room temperature (Remote controller) ˚C Air Temperature (TA) ˚C [0024]=24 ˚C Coil Temperature (TCJ)
  • Page 52 FILE NO. SVM-13085 Target outdoor unit (SMMS-i – Series 4) CODE No. Data Format Unit Remote controller display example Indoor unit Room temperature (in control) ˚C data *2 Room temperature (Remote controller) ˚C Air Temperature (TA) ˚C Coil Temperature (TCJ) ˚C [0024]=24 ˚C Coil Temperature (TC2)
  • Page 53 FILE NO. SVM-13085 CODE No. Data Format Unit Remote controller display example U1 U2 U3 U4 Individual Rotation of compressor 1 data 2 of [0642]=64.2 rps Rotation of compressor 2 outdoor unit — Rotation of compressor 3 [0058]=Mode 58 Outdoor fan mode Mode Heat sink temperature of compressor 54 64 74 84...
  • Page 54 FILE NO. SVM-13085 LED display on P.C. board 1. D501 (Red) D501 goes on at the same time when the power supply is turned on. (Goes on with operation of the main microprocessor) D501 flashes with 1-second interval (every 0.5 second) : When there is no EEPROM or write-in error D501 flashes with 10-seconds interval (every 5 second) : In DISP mode D501 flashes with 2-seconds interval (every 1 second) : During setting of function exchange (EEPROM)
  • Page 55: Troubleshooting

    FILE NO. SVM-13085 8. TROUBLESHOOTING 8-1. Troubleshooting Summary 1. Before troubleshooting 1) Applied models SMMS (i) Multi type models Indoor unit : MMX-APXXX, Outdoor unit : MMY-MAPXXXXT8X, MMY-MAPXXXHT7X Super Heat Recovery Multi type models Indoor unit : MMX-APXXX, Outdoor unit : MMY-MAPXXXFT8X Mini-SMMS Multi type models Indoor unit : MMX-APXXX,...
  • Page 56 FILE NO. SVM-13085 – 56 – SVM-13085.indb 56 SVM-13085.indb 56 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 57 FILE NO. SVM-13085 – 57 – SVM-13085.indb 57 SVM-13085.indb 57 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 58 FILE NO. SVM-13085 List of check codes (outdoor unit) IPDU: Intelligent Power Drive Unit (Inverter P.C. board) (Errors detected by SMMS outdoor interface - typical examples) : Flashing, : Goes off :Lighting, ALT.: Flashing is alternately when there are two flashing LED SIM: Simultaneous flashing when there are two flashing LED Check code Display of receiving unit...
  • Page 59 FILE NO. SVM-13085 Check code Display of receiving unit TCC-LINK Outdoor 7-segment display Indicator light block central control Typical fault site Description of error or main remote Operation Timer Ready Sub-code Flash controller display Outdoor suction Outdoor suction temperature sensor (TS1) has –...
  • Page 60 FILE NO. SVM-13085 Check code Display of receiving unit TCC-LINK Outdoor 7-segment display Indicator light block central control Typical fault site Description of error or main remote Operation Timer Ready Flash Sub-code controller display Address setting has not been performed for one or SIM Indoor group address not –...
  • Page 61 FILE NO. SVM-13085 (Errors detected by IPDU featuring in SMMS standard outdoor unit - typical examples) Check code Display of receiving unit TCC-LINK Outdoor 7-segment display Indicator light block central control Typical fault site Description of error or main remote OperationTimer Ready Flash Sub-code...
  • Page 62 FILE NO. SVM-13085 8-3. Troubleshooting by check Display on Remote Controller In case of wired remote controller (RBC-AMT32E) 1. Confirmation and check When a trouble occurred on the air conditioner, the check code and the indoor unit No. are displayed on the display section of the remote controller.
  • Page 63 FILE NO. SVM-13085 In case of central remote controller (TCB-SC642TLE2) ZONE ZONE GROUP CODE 1234 TEST UNIT No. SET DATA SETTING R.C. GROUP SELECT ZONE 1. Confirmation and check When a trouble occurred on the air conditioner, the check code and the indoor unit No. are displayed on the display section of the remote controller.
  • Page 64 FILE NO. SVM-13085 Indoor unit display part (Receiving unit) (Wireless type) When specifying the check code, check 7-segment display on the center unit. For the check code which is not displayed on the outdoor 7-segment, confirm it in Section “ 8-2 How to Check / Check code display list (Indoor unit) ”.
  • Page 65 FILE NO. SVM-13085 Lamp indication Check code Cause of trouble occurrence ⎫ Operation Timer Ready Heat exchanger sensor (TCJ) error ⎪ ⎪ Heat exchanger sensor (TC2) error ⎬ Temp. sensor error in indoor unit ⎪ Heat exchanger sensor (TC1) error ⎪...
  • Page 66 FILE NO. SVM-13085 Others (Except check code) Lamp indication Check code Cause of trouble occurrence Operation Timer Ready — During test run Simultaneous flash Operation Timer Ready COOL/HEAT disagreement — (Automatic cooling/heating setup to automatic cooling/heating unavailable model, heating setup to cooling only model) Alternate flash –...
  • Page 67 FILE NO. SVM-13085 8-4. Check codes displayed on remote controller and SMMS outdoor unit (7-segment display on I/F board) and locations to be checked For other types of outdoor units, refer to their own service manuals. Check code Location Error detection Outdoor 7-segment display Main Description...
  • Page 68 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Duplicated Indoor Duplicated All stop More than one indoor unit is Check indoor addresses. unit indoor address assigned same address.
  • Page 69 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Indoor Error in Stop of Periodic communication Check remote controller wiring. unit communication corresponding between indoor header and Check indoor power supply between indoor unit...
  • Page 70 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code SMMS (Series 1) IPDU All stop Communication is disrupted Check wiring and connectors 01: A3-IPDU1 error communication between IPDUs (P.C.
  • Page 71 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code TL sensor All stop Sensor resistance is infinity Check connection of TL sensor error connector. or zero (open / short circuit).
  • Page 72 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Pd sensor All stop Output voltage of Pd Check connection of Pd error sensor is zero (sensor sensor connector.
  • Page 73 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Low oil level All stop Operating compressor <All outdoor units in protection detects continuous state of corresponding line to be low oil level for about 2 hours.
  • Page 74 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Compressor 2 All stop Compressor 2 case Check Compressor 2 case thermo case thermo circuit. thermo was activation activated.
  • Page 75 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code SMMS Oil detection All stop The temperature Check the TK1 sensor installation. Check the TK1 sensor resistant (1 series) circuit error change of TK1...
  • Page 76 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code SMMS-i Oil level All stop No temperature Check for disconnection of TK4 sensor. detection change is detected (4 series) Check resistance characteristics of circuit error...
  • Page 77 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Outdoor All stop Jumper wire provided on P.C. Check model setting of P.C. capacity not set board for servicing I/F P.C.
  • Page 78 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Detected indoor Indoor External Stop of Signal is present at When external device is address unit interlock of corresponding...
  • Page 79 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Open phase detected, All stop Phase sequence Check the phase sequence of Phase sequence error error was detected outdoor power wiring.
  • Page 80 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Outdoor liquid All stop <During cooling operation> Check full-close operation backflow When system is in cooling of outdoor PMV (1, 2, 4).
  • Page 81 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code Detected 4-way valve All stop Abnormal refrigerating cycle Check for defect in main outdoor unit reversing error data is collected during body of 4-way valve.
  • Page 82 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code SMMS (Series 1) Outdoor fan All stop (Sub code: 08) Check the fan motor. Check the connector 08: Out of step IPDU error FAN IPDU position detection...
  • Page 83 FILE NO. SVM-13085 Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection controller Sub-code code ∗ SMMS-i IPDU Outdoor fan All stop Check fan motor. (Sub code: 0 (Series 4) Check for defect in fan IPDU error Fan IPDU over current...
  • Page 84: Errors Detected By Tcc-Link Central Control Device

    FILE NO. SVM-13085 Errors detected by TCC-LINK central control device Check code Location Error detection Outdoor 7-segment display Main Description System status Check items (locations) condition(s) remote Check detection Sub-code controller code TCC-LINK TCC-LINK Continued Central control device is Check for defect in central central control operation unable to transmit signal.
  • Page 85 FILE NO. SVM-13085 8-5 Diagnostic Procedure for Each Check Code (Indoor Unit) *Please refer to the multi outdoor unit service manual excluding these. Check code [E11 error] Is the connection for the UART communication Repair of connector connector (Internal board connection.
  • Page 86 FILE NO. SVM-13085 [P12 error] Power off. Is not connection error or Repair the connector disconnection on the connector connection. CN210 of indoor unit P.C. board? Disconnect the connector CN210 to the indoor P.C. board Does the Replace the indoor fan turn smoothly when fan motor.
  • Page 87: Indoor Unit

    FILE NO. SVM-13085 Sensor charateristics Indoor unit Temperature sensor characteristics Indoor TA sensor Temperature [˚C] Resistance [kΩ] 33.9 Resistance 26.1 [kΩ] 20.3 15.9 12.6 10.0 Temperature [˚C] Temperature [˚C] Resistance [kΩ] –20 99.9 –15 74.1 Indoor TC1 sensor –10 55.6 –5 42.2 32.8...
  • Page 88 FILE NO. SVM-13085 <Maintenance/Check list> Aiming in environmental preservation, it is strictly recommended to clean and maintain the indoor/outdoor units of the operating air conditioning system regularly to secure effective operation of the air conditioner. It is also recommended to maintain the units once a year regularly when operating the air conditioner for a long time.
  • Page 89: Detachments

    FILE NO. SVM-13085 9. DETACHMENTS DANGER CAUTION Before carrying out the repair or removal Be sure to put on the gloves at work, be sure to set the circuit breaker to disassembling work; otherwise an injury the OFF position. will be caused by a part, etc. Otherwise, electric shocks may result.
  • Page 90 FILE NO. SVM-13085 Part name Procedure Remarks Electric parts box Electric parts 1. Detachment P.C. board 1) Perform works of 1 of 2) Remove the screws of electric parts box. 3) Draws out forward after the electric box is moved in the direction of the arrow, and the back of the part electric part boxis hung on the edge of the Terminal block...
  • Page 91 FILE NO. SVM-13085 Part name Procedure Remarks Fan, Quantity of fan Fan case, Shaft, Model Installation Bearing AP015, AP018 Fan motor both sides AP024, AP027 One of shafts are bearings. The shaft middle part is AP036, AP056 supported in the bearing. 1.
  • Page 92 FILE NO. SVM-13085 Part name Procedure Remarks 3) When the bearing is installed in the shaft, perform work of 1) . The coupling side is set to the ditch and the fan is fixed with the hexagonal screw hole. NOTE The ditch of shaft The ditch of shaft Be sure to use a torque wrench for...
  • Page 93 FILE NO. SVM-13085 Part name Procedure Remarks Fan motor 1. Detachment 1) Perform works of 1 of 2) Remove connectors for fan motor wiring from control P.C. board. CN210 : Motor power supply (7P: White) NOTE First unlock the housing and then remove the connectors.
  • Page 94 FILE NO. SVM-13085 Part name Procedure Remarks Side cover 1. Detachment 1) Perform works of 1 of 1. 2) Remove the screws of the side cover. (One side: Ø4 x 10, 1 pc.) 3) Slide to the air discharge side, remove the side cover.
  • Page 95 FILE NO. SVM-13085 Part name Procedure Remarks Under panel 1. Detachment 1) Perform works of 1 of 2) Remove the support plate. (AP024 to AP056 type only) (Ø4 x 10, 1 pc.) Square hole Front side screw The screw on a front side is removed, and it detaches it from the square hole on the back side.
  • Page 96 FILE NO. SVM-13085 Part name Procedure Remarks Drain pan 1. Detachment 1) Perform works of 1 of 1, 1 of 7 and 1 of 8. 2) Remove the drain cap and then extract the drain water accumulated in the drain pan. Drain cap NOTE When removing the drain cap, be sure to...
  • Page 97 FILE NO. SVM-13085 Part name Procedure Remarks PMV motor PMV connector 1. Detachment (Pulse 1) Recover the refrigerant gas. Motor Valve) 2) Perform work of 1 of 1, 1 of 2, 1 of 7, 1 of 8 and 1 of 9. 3) Remove the PMV connector (CN82, Lead clamp Blue, 6P) from the control P.C.
  • Page 98: Replacement Of Service P.c. Board

    FILE NO. SVM-13085 No. Part name Procedure Remarks Heat 1. Detachment exchanger 1) Recover the refrigerant gas and then remove the refrigerant pipe of the indoor unit. 2) Perform works of 1 of Pull out sensor wires from the holder. 3) The screw that is the fixing of the piping support is removed, and the piping support is removed.
  • Page 99 FILE NO. SVM-13085 10. REPLACEMENT OF SERVICE P.C. BOARD CAUTION <Model name: MMC-AP∗∗∗HP∗> <Note: when replacing the P.C. board for indoor unit servicing> The nonvolatile memory (hereafter called EEPROM, IC503) on the indoor unit P .C. board before replacement includes the model specific type information and capacity codes as the factory-set value and the important setting data which have been automatically or manually set when the indoor unit is installed, such as system/ indoor/group addresses, high ceiling select setting, etc.
  • Page 100 FILE NO. SVM-13085 [1] Setting data read out from EEPROM The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out. TEST Step 1 Push button on the remote controller simultaneously for more than 4 seconds. ∗...
  • Page 101 FILE NO. SVM-13085 (Case 1) B) In case that power of the indoor units cannot be turned on individually a) Remove temporarily the group wire connected to the terminal blocks A and B of the exchanged indoor unit. b) After connecting the remote controller wire only to the removed terminal block, turn on power of the indoor units and proceed to [3].
  • Page 102 FILE NO. SVM-13085 Step 4 Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2 above again. Step 5 Change the CODE No. (DN) to “ ” by pushing buttons for the temperature setting. (this is the setting for the filter sign lighting time.) Step 6 Check the setting data displayed at this time with the setting data put down in [1].
  • Page 103: Exploded Views And Parts List

    FILE NO. SVM-13085 Table 1. Setting data (CODE No. table (example)) Item Setting data Factory-set value Filter sign lighting time Depending on Type Filter pollution level 0000: standard Central control address 0099: Not determined 0002: +2°C Heating suction temperature shift (flooring installation type: 0) Cooling only 0000: Heat pump...
  • Page 104 FILE NO. SVM-13085 11. EXPLODED VIEWS AND PARTS LIST 11-1. MMC-AP0157HP-E, MMC-AP0187HP-E MMC-AP0157HP-TR, MMC-AP0187HP-TR – 104 – SVM-13085.indb 104 SVM-13085.indb 104 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 105 FILE NO. SVM-13085 MMC-AP Ref.No. Part No. Description 0157HP-E 0187HP-E 0157HP-TR 0187HP-TR 43T72314 ASM-SUB-PAN-DR 43T44513 ASM-REF 43T02301 ASM-P-SIDE-R 43T02302 ASM-P-SIDE-L 43T07313 ASM-SUP-FLAP 43T07314 SUP-SHAFT 43T07315 HINGE-GRILLE 43T07316 HOOK-GRILLE 43T08420 LED-BASE 43T08421 PANEL-LED 43T09493 SUCTION-GRILLE 43T00638 ASM-COAT-P-UP 43T00641 ASM-COAT-P-UD 43T11326 ASM-FORM-UP 43T11329 ASM-FORM 43T11330...
  • Page 106: Electric Parts

    FILE NO. SVM-13085 Electric Parts MMC-AP Ref.No. Part No. Description 0157HP-E 0187HP-E 0157HP-TR 0187HP-TR SENSOR ASSY, 43T50347 SERVICE 43T60435 SERV-TERMINAL 43T60362 TERMINAL 43T62348 COVER-E-BOX 43T50351 HOLDER-TA 43T61317 BASE-CLAMP 43T6V442 PC BOARD ASSY 43459017 ASM-PCB(OP) 43T50476 SERVICE-SENSOR 43T50477 SERVICE-SENSOR – 106 – SVM-13085.indb 106 SVM-13085.indb 106 12/24/13 10:56 AM...
  • Page 107 FILE NO. SVM-13085 11-2. MMC-AP0247HP-E, MMC-AP0277HP-E MMC-AP0247HP-TR, MMC-AP0277HP-TR – 107 – SVM-13085.indb 107 SVM-13085.indb 107 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 108 FILE NO. SVM-13085 MMC-AP Ref.No. Part No. Description 0247HP-E 0277HP-E 0247HP-TR 0277HP-TR 43T72315 ASM-SUB-PAN-DR 43T44514 ASM-REF 43T02301 ASM-P-SIDE-R 43T02302 ASM-P-SIDE-L 43T07313 ASM-SUP-FLAP 43T07314 SUP-SHAFT 43T07315 HINGE-GRILLE 43T07316 HOOK-GRILLE 43T08420 LED-BASE 43T08421 PANEL-LED 43T09493 SUCTION-GRILLE 43T09494 SUCTION-GRILLE 43T00639 ASM-COAT-P-UP 43T00642 ASM-COAT-P-UD 43T11327 ASM-FORM-UP 43T11329...
  • Page 109 FILE NO. SVM-13085 Electric Parts MMC-AP Ref.No. Part No. Description 0247HP-E 0277HP-E 0247HP-TR 0277HP-TR SENSOR ASSY, 43T50347 SERVICE 43T60435 SERV-TERMINAL 43T60362 TERMINAL 43T62348 COVER-E-BOX 43T50351 HOLDER-TA 43T61317 BASE-CLAMP 43T6V442 PC BOARD ASSY 43459017 ASM-PCB(OP) 43T50476 SERVICE-SENSOR 43T50477 SERVICE-SENSOR – 109 – SVM-13085.indb 109 SVM-13085.indb 109 12/24/13 10:56 AM...
  • Page 110 FILE NO. SVM-13085 11-3. MMC-AP0367HP-E, MMC-AP0487HP-E, MMC-AP0567HP-E MMC-AP0367HP-TR, MMC-AP0487HP-TR, MMC-AP0567HP-TR – 110 – SVM-13085.indb 110 SVM-13085.indb 110 12/24/13 10:56 AM 12/24/13 10:56 AM...
  • Page 111 FILE NO. SVM-13085 MMC-AP Ref.No. Part No. Description 0367HP-E 0487HP-E 0567HP-E 0367HP-TR 0487HP-TR 0567HP-TR 43T72316 ASM-SUB-PAN-DR 43T44515 ASM-REF 43T02301 ASM-P-SIDE-R 43T02302 ASM-P-SIDE-L 43T07313 ASM-SUP-FLAP 43T07314 SUP-SHAFT 43T07315 HINGE-GRILLE 43T07316 HOOK-GRILLE 43T08420 LED-BASE 43T08421 PANEL-LED 43T09494 SUCTION-GRILLE 43T00640 ASM-COAT-P-UP 43T00643 ASM-COAT-P-UD 43T11328 ASM-FORM-UP 43T11329...
  • Page 112 FILE NO. SVM-13085 Electric Parts MMC-AP Ref.No. Part No. Description 0487HP-TR 0567HP-TR 0367HP-E 0487HP-E 0567HP-E 0367HP-TR SENSOR ASSY, 43T50347 SERVICE 43T60435 SERV-TERMINAL 43T60362 TERMINAL 43T62348 COVER-E-BOX 43T50351 HOLDER-TA 43T61317 BASE-CLAMP 43T6V442 PC BOARD ASSY 43459017 ASM-PCB(OP) 43T50476 SERVICE-SENSOR 43T50477 SERVICE-SENSOR –...
  • Page 113 FILE NO. SVM-13085 WARNINGS ON REFRIGERANT LEAKAGE Check of Concentration Limit Important The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas NOTE 2 : leaking out, its concentration will not exceed a set limit. The standards for minimum room volume are as follows.
  • Page 114 TOSHIBA CARRIER (THAILAND) CO.,LTD. 144/9 MOO 5, BANGKADI INDUSTRIAL PARK, TIVANON ROAD, TAMBOL BANGKADI, AMPHUR MUANG, PATHUMTHANI 12000, THAILAND. SVM-13085.indb 114 SVM-13085.indb 114 12/24/13 10:56 AM 12/24/13 10:56 AM...