13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of "Input/Output" (...continuation)
Screen Parameter
I08cr
CR_DIN01_DEBUG
I08cr
CR_DIN02_DEBUG
I08cr
CR_DIN03_DEBUG
I08cr
DIN25_M8_C_F_DEBUG Status of digital input: remote Cooling/Heating
I10cr
COMPRESOR_REC
I10cr
OUT_VIC_CR
I10cr
RELE_ALARMA_CR
I10cr
DOUT19
I10cr
DOUT20
I10cr
DOUT18
I02zn
TEMP_TCO11
I02zn
TEMP_TCO12
I02zn
TEMP_TCO13
I02zn
TEMP_TCO14
I03zn
TEMP_RET_Z1
I03zn
TEMP_RET_Z2
I03zn
TEMP_RET_Z3
I03zn
TEMP_RET_Z4
COMPUERTA_IMP_
I08zn
ZONA1_ABIERTA
COMPUERTA_IMP_
I08zn
ZONA2_ABIERTA
COMPUERTA_IMP_
I08zn
ZONA3_ABIERTA
COMPUERTA_IMP_
I08zn
ZONA4_ABIERTA
ZONIF_4Z_UPC2.
I08zn
IN_DIG05_INC
ZONIF_4Z_UPC2.
I08zn
IN_DIG06_RTVI
ZONIF_4Z_UPC2.
I08zn
IN_DIG07_ON_OFF
COMPUERTA_IMP_
I09zn
ZONA1_ABIERTA
COMPUERTA_IMP_
I09zn
ZONA2_ABIERTA
COMPUERTA_IMP_
I09zn
ZONA3_ABIERTA
COMPUERTA_IMP_
I09zn
ZONA4_ABIERTA
I09zn
ZONIF_4Z_UPC2.DOUT5 Status of output No.5 of SMALL board (addr.11) (air fl ow zoning)
I09zn
ZONIF_4Z_UPC2.DOUT6 Status of output No.6 of SMALL board (addr.11) (air fl ow zoning)
ZONIF_4Z_UPC2.RELE_
I09zn
ALARMA_4Z
A2L_SENSOR_
I19
PERCENT_LFL
A2L_SENSOR_
I19
PERCENT_VOL
I19
A2L_SENSOR_TEMP
I19
A2L_SENSOR_LIFE
Parameters of "Access Levels"
Screen Parameter
NA01
ACTUAL_ACCES_LEVEL
NA01
NOT_PASS_ACCESS_LEVEL_1
NA01
MASK_ACCES_LEVEL_1
NA01
NOT_PASS_ACCESS_LEVEL_2
NA01
MASK_ACCES_LEVEL_2
NA01
NOT_PASS_ACCESS_LEVEL_3
NA01
MASK_ACCES_LEVEL_3
40
Description of the parameter
Status of digital input: remote On/Off
Status of digital input: high pressure switch of the recovery circuit
Status of digital input: compressor thermal protection of the recovery circuit
Status of digital output: Contactor of the recovery compresor
Status of digital output: cycle reversing valve of recovery compresor
Status of digital output: alarm relay
Status of digital output 19: compressor with supplementary crankcase heater
Status of digital output 20: electrical heater for protection of fresh air damper or
solenoid valve SV1 with actve dehumidifi cation
Status of digital output 18: electical heating for the piping layout of the water
circuit with GREAT COLD or confi gurable output (humidifi er, HWC pump,
alarm signal,...)
Display of the temperature meaured by User terminal on zone 1 (air zoning)
Display of the temperature meaured by User terminal on zone 2 (air zoning)
Display of the temperature meaured by User terminal on zone 3 (air zoning)
Display of the temperature meaured by User terminal on zone 4 (air zoning)
Display of the NTC probe return temperature (optional) of zone 1 (air zoning)
Display of the NTC probe return temperature (optional) of zone 2 (air zoning)
Display of the NTC probe return temperature (optional) of zone 3 (air zoning)
Display of the NTC probe return temperature (optional) of zone 4 (air zoning)
Status of digital input 01 of SMALL board (addr.11): air fl ow zoning
Status of digital input 02 of SMALL board (addr.11): air fl ow zoning
Status of digital input 03 of SMALL board (addr.11): air fl ow zoning
Status of digital input 04 of SMALL board (addr.11): air fl ow zoning
Status of digital input 05 of SMALL board (addr.11): air fl ow zoning
Status of digital input 06 of SMALL board (addr.11): air fl ow zoning
Status of digital input 07 of SMALL board (addr.11): air fl ow zoning
Status of supply damper of zone 1 (air fl ow zoning)
Status of supply damper of zone 2 (air fl ow zoning)
Status of supply damper of zone 3 (air fl ow zoning)
Status of supply damper of zone 4 (air fl ow zoning)
Status of alarm relay of SMALL board (addr.11) (air fl ow zoning)
Percentage LFL of A2L sensor (leak detector R-454B)
Volume percentage of A2L sensor (R-454B leak detector)
A2L sensor temperature (R-454B leak detector)
A2L Sensor Life (R-454B leak detector)
Description of the parameter
Current access level
Without access to level 1
Access to level 1
Without access to level 2
Access to level 2
Without access to level 3
Access to level 3
E
INPUTS/OUTPUTS
Value Min.
0
0
0
0
0
0
0
0
0
0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0.0
0.0
0.0
0
K
PASSWORDS
Value Min. Max.
1
0
0
0
0
0
0
Max. UOM Type
R/W
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
-99.9
99.9
°C
Analog. R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
0
1
---
Digital R
-999.9 999.9 %
Analog. R
-999.9 999.9 %
Analog. R
-999.9 999.9 °C
Analog. R
0
32767 ---
Integer R
UOM Type
R/W
1
9
---
Integer R
0
1
---
Digital R/W
0
1
---
Digital R/W
0
1
---
Digital R/W
0
1
---
Digital R/W
0
1
---
Digital R/W
0
1
---
Digital R/W
Add.
BMS
117
278
294
295
296
297
299
300
301
302
316
317
318