13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of "Summer/Winter"
Screen Parameter
FC01
SEL_FRIO_CALOR
FC01
MODO_FRIO_CALOR_AUTO
FC01
CALOR_FRIO_PANEL
FC01
SET_TEMP_EXT_CAMBIO_FRIO
FC01
SET_TEMP_EXT_CAMBIO_CALOR Outdoor temperature setpoint for change to HEATING mode (in AUTO mode) 20.0
PGD1_bloqueado_SEL_FRIO_
FC01
CALOR
FC01
ON_VENT_100_AE_REMOTO
Parameters of "Clock/Scheduler"
Screen Parameter
PH01
TIPO_RELOJ
PH01
NEW_HOUR
PH01
NEW_MINUTE
PH01
NEW_DAY
PH01
NEW_MONTH
PH01
NEW_YEAR
PH01
DIA_SEMANA
PH01
NEW_DATE_MSK
PH02
TZ_Idx
PH03
TIPO_PROG_HORARIA
PH03
ARR_FORZADO
PH03
TIME_ARR_FORZADO
HAB_BLOQ_COMP_ON_FASE_LIM_
PH03
FRIO
HAB_BLOQ_RENOVACION_ON_FASE_
PH03
LIM
PH04
H_ARR_1A
PH04
M_ARR_1A
PH04
H_PAR_1A
PH04
M_PAR_1A
PH04
H_ARR_1B
PH04
M_ARR_1B
PH04
H_PAR_1B
PH04
M_PAR_1B
PH04
H_ARR_1C
PH04
M_ARR_1C
PH04
H_PAR_1C
PH04
M_PAR_1C
PH05
H_ARR_2A
PH05
M_ARR_2A
PH05
H_PAR_2A
PH05
M_PAR_2A
PH05
H_ARR_2B
PH05
M_ARR_2B
PH05
H_PAR_2B
PH05
M_PAR_2B
PH05
H_ARR_2C
PH05
M_ARR_2C
PH05
H_PAR_2C
B
Description of the parameter
Procedures for the selection of the COOLING/HEATING mode:
0: by keyboard
1: remote (by digital input)
2: auto
3: only ventilation
4: ventilation 100% fresh air
5: SHRD shared network
COOLING/HEATING selection in AUTO:
0: by indoor temperature; 1: by outdoor temperature
COOLING/HEATING selection by keyboard:
0: HEATING (winter); 1: COOLING (summer)
Outdoor temperature setpoint for change to COOLING mode (in AUTO mode) 22.0
Enabling of the blocking of summer / winter selection in the Graphic terminal
(so that the fi nal user cannot change it)
Enabling of the VENTILATION mode with 100% fresh air remotely (analog
input U2 of the c.pCOe expansion card with address 8)
L
Description of the parameter
Type of clock (No, Actual)
Setting the clock: new hour
Setting the clock: new minute
Setting the clock: new day
Setting the clock: new month
Setting the clock: new year
Day of the week
Confi rm time change
Index used to change the time zone (management change from
winter to summer and vice versa automatically)
Type of start-up:
0 = ON/OFF schedule
1 = Schedule only setpoint change
2 = ON/OFF schedule with limit SET of ON
3 = Forced
4 = 3 setpoints schedule + OFF of unit
Forced start-up
On time with forced start-up
Disable the compressors in summer with "ON/OFF schedule with
limit SET of ON" (nocturnal freecooling)
Disable the outdoor air renewal with "ON/OFF schedule with limit
SET of ON" (nocturnal operation)
Start-up hour of slot 1- program 1
Start-up minute of slot 1-program 1
Stop hour of slot 1 - program 1
Stop minute of slot 1 - program 1
Start-up hour of slot 2 - program 1
Start-up minute of slot 2 - program 1
Stop hour of slot 2 - program 1
Stop minute of slot 2 - program 1
Start-up hour of slot 3 - program 1
Start-up minute of slot 3 - program 1
Stop hour of slot 3 - program 1
Stop minute of slot 3 - program 1
Start-up hour of slot1 - program 2
Start-up minute of slot 1 - program 2
Stop hour of slot 1 - program 2
Stop minute of slot 1 - program 2
Start-up hour of slot 2 - program 2
Start-up minute of slot 2 - program 2
Stop hour of slot 2 - program 2
Stop minute of slot 2 - program 2
Start-up hour of slot 3 - program 2
Start-up minute of slot 3 - program 2
Stop hour of slot 3 - program 2
HCCONFIG
Value Min. Max. UOM Type
2
1
1
0
0
SCHEDULE
Value Min. Max.
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
52
1
3
0
0
0
2
1
0
0
0
0
6
0
30
0
11
0
0
0
11
0
30
0
13
0
30
0
15
0
0
0
19
0
0
0
8
0
0
0
14
0
0
0
17
0
0
0
20
0
30
0
0
0
0
0
0
0
Add.
R/W
BMS
0
5
---
Integer R/W 59
0
1
---
Digital R/W 232
0
1
---
Digital R/W 66
99.9 99.9 °C
Analog. R/W 223
99.9 99.9 °C
Analog. R/W 222
0
1
---
Digital R/W 240
0
1
---
Digital R
Add.
UOM Type
R/W
BMS
2
---
Integer R/W 57
23
h
Integer R/W 119
59
min
Integer R/W 120
31
day
Integer R/W 121
12
month Integer R/W 122
99
year
Integer R/W 123
0
day
Integer R/W 52
1
---
Digital R/W
TZ_
---
Integer R
IdxMax
4
---
Integer R/W 71
1
---
Digital R/W 120
999
h
Integer R/W 73
1
---
Digital R/W 72
1
---
Digital R/W 73
23
h
Integer R/W 74
59
min
Integer R/W 75
23
h
Integer R/W 76
59
min
Integer R/W 77
23
h
Integer R/W 78
59
min
Integer R/W 79
23
h
Integer R/W 80
59
min
Integer R/W 81
23
h
Integer R/W 82
59
min
Integer R/W 83
23
h
Integer R/W 84
59
min
Integer R/W 85
23
h
Integer R/W 86
59
min
Integer R/W 87
23
h
Integer R/W 88
59
min
Integer R/W 89
23
h
Integer R/W 90
59
min
Integer R/W 91
23
h
Integer R/W 92
59
min
Integer R/W 93
23
h
Integer R/W 94
59
min
Integer R/W 95
23
h
Integer R/W 96
33

Advertisement

Table of Contents
loading

This manual is also suitable for:

50ff 02050ff 28050fc 02050fc 28050nc 02250nc 118

Table of Contents