13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of "Input/Output" (...continuation)
Screen Parameter
I05c
T_P_LP_C1_AIN06
I05c
TEMP_CAL_LP_C1_AIN06
I05c
T_P_LP_C2_AIN09
I05c
TEMP_CAL_LP_C2_AIN09
I05e
TEMP_ASP_C1_AIN08
I05e
SHTemp_A
I05e
TEMP_ASP_C2_AIN11
I05e
SHTemp_B
I05f
TEMP_ASP_C2_AIN11
I06a
T_P_HP_C1
I06a
TEMP_CAL_HP_C1
I06a
COMPRESOR_1
I06a
COMPRESOR_1_2
I06a
TEMP_ASP_C1_EVOS
I06a
T_P_LP_C1_EVOS
I06a
TEMP_CAL_LP_C1_EVOS
I06a1
I4_EEV_POSITION_STEP
I06a1
A17_EEV_POSITION_PERCENT
I06a1
EVD1_RegStatus
I06a1
EVD1_ProtStatus
I06a1
SH_A_EVOS
I06b
T_P_HP_C2
I06b
TEMP_CAL_HP_C2
I06b
COMPRESOR_2
I06b
COMPRESOR_2_2
I06b
TEMP_ASP_C2_EVOS
I06b1
T_P_LP_C2_EVOS
I06b1
TEMP_CAL_LP_C2_EVOS
I06b1
I149_EEV_POSITION_STEP_2ND
I06b1
A66_EEV_POSITION_PERCENT_2ND Valve opening (%) of circuit 2
I06b1
EVD2_RegStatus
I06b1
EVD2_ProtStatus
I06b1
SH_B_EVOS
I06c1
TEMP_ASP_C1_EVOS
I06c1
SH_A_EVOS
I06e
T_P_LP_C1_EVOS
I06e
TEMP_CAL_LP_C1_EVOS
I06f
TEMP_ASP_C2_EVOS
I06f
SH_B_EVOS
I06g
T_P_LP_C2_EVOS
I06g
TEMP_CAL_LP_C2_EVOS
I07
N_HOR_ON_EQUIPO
I07
N_HOR_COMP1
I07
N_HOR_COMP1_2
I07a
N_HOR_COMP2
I07a
N_HOR_COMP2_2
I07a
N_HOR_CR
I08
DIN01_RTVI
I08
DIN02_INC
I08
DIN03_AP1
I08
DIN04_TC1
I08
DIN05_TS_IC
I08
DIN06_FS
I08
DIN07_ON_OFF
I08
DIN08_AH_BAC_REC_ROT
I08
DIN09_AP2
I08
DIN10_TC2
I08a
DIN21_OFF_1ET
I08a
DIN_OFF_2ET
E
Description of the parameter
Display of the low pressure transducer of circuit 1
Calculated temperature for low pressure of circuit 1
Display of the low pressure transducer of circuit 2
Calculated temperature for low pressure of circuit 2
Display of the suction temperature of circuit 1
Display of overheating of circuit 1
Display of the suction temperature of circuit 2
Display of overheating of circuit 2
Display of the outdoor coil temperature (1-circuit units)
Display of the high pressure transducer of circuit 1
Calculated temperature for high pressure of circuit 1
Contactor of compressor 1 circuit 1
Contactor of compressor 2 circuit 1
Suction temperature on circuit 1
Evaporating pressure on circuit 1
Evaporating temperature on circuit 1
Valve position (steps) of circuit 1
Valve opening (%) of circuit 1
Status of circuit 1 valve
Status of circuit 1 valve protection
Overheating on the expansion valve of circuit 1
Display of the high pressure transducer of circuit 2
Calculated temperature for high pressure of circuit 2
Contactor of compressor 1 circuit 2
Contactor of compressor 2 circuit 2
Suction temperature on circuit 2
Evaporating pressure on circuit 2
Evaporating temperature on circuit 2
Valve position (steps) of circuit 2
Status of circuit 2 valve
Status of circuit 2 valve protection
Overheating on the expansion valve of circuit 1
Suction temperature on circuit 1
Overheating on the expansion valve of circuit 1
Evaporating pressure on the circuit 1 valve
Evaporating temperature on the circuit 1 valve
Suction temperature on circuit 2
Overheating on the expansion valve of circuit 2
Evaporating pressure on the circuit 2 valve
Evaporating temperature on the circuit 2 valve
Display of operating hours of unit
Display of operating hours of compressor 1 circuit 1
Display of operating hours of compressor 2 circuit 1
Display of operating hours of compressor 1 circuit 2
Display of operating hours of compressor 2 circuit 2
Display of operating hours of recovery compressor
Status of digital input 1: supply fan thermal protection
Status of digital input 2: gas detector
Status of digital input 3: high pressure circuit 1
Status of digital input 4: thermal protection of compressors and
outdoor fans of circuit 1
Status of digital input 5: safety of el. heaters / burner / boiler
Status of digital input 6: clogged fi lters detector
Status of digital input 7: remote ON/OFF
Status of digital input 8: antifreeze safety of the hot water coil (HWC) 0
Status of digital input 9: high pressure circuit 2
Status of digital input 10: thermal protection of compressors and
outdoor fans of circuit 2
Status of digital input 21: disconnection of 1 compressor stage
Status of digital input 22: disconnection of 2 compressor stages 0
INPUTS/OUTPUTS
Value Min.
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
00.0
-99.9
0.0
-99.9
00.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0
0
0
0
0.0
-99.9
0.0
-99.9
0.0
-99.9
0
-9999
0.0
0.0
0
-32768 32767 ---
0
-32768 32767 ---
0.0
-99.9
0.0
-99.9
0.0
-99.9
0
0
0
0
0.0
-99.9
0.0
-99.9
0.0
-99.9
0
-9999
0.0
0.0
0
-32768 32767 ---
0
-32768 32767 ---
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
Add.
Max. UOM Type
R/W
BMS
99.9
bar
Analog. R
204
99.9
---
Analog. R
206
99.9
bar
Analog. R
205
99.9
---
Analog. R
207
99.9
---
Analog. R
251
99.9
---
Integer R
99.9
---
Analog. R
252
99.9
---
Integer R
99.9
---
Analog. R
252
99.9
bar
Analog. R
3
99.9
°C
Analog. R
123
1
---
Digital R
16
1
---
Digital R
76
99.9
°C
Analog. R
99.9
bar
Analog. R
99.9
°C
Analog. R
9999 ---
Integer R
100.0 %
Analog. R
255
Integer R
Integer R
99.9
K
Analog. R
253
99.9
bar
Analog. R
4
99.9
°C
Analog. R
124
1
---
Digital R
17
1
---
Digital R
77
99.9
°C
Analog. R
99.9
bar
Analog. R
99.9
°C
Analog. R
9999 ---
Integer R
100.0 %
Analog. R
256
Integer R
Integer R
99.9
K
Analog. R
254
99.9
°C
Analog. R
99.9
K
Analog. R
253
99.9
bar
Analog. R
99.9
°C
Analog. R
99.9
°C
Analog. R
99.9
K
Analog. R
254
99.9
bar
Analog. R
99.9
°C
Analog. R
32767 h
Integer R
62
32767 h
Integer R
10
32767 h
Integer R
53
32767 h
Integer R
11
32767 h
Integer R
69
32767 h
Integer R
12
1
---
Digital R
12
1
---
Digital R
135
1
---
Digital R
1
1
---
Digital R
5
1
---
Digital R
7
1
---
Digital R
11
1
---
Digital R
1
---
Digital R
1
---
Digital R
2
1
---
Digital R
6
1
---
Digital R
1
---
Digital R
37