13 - LIST OF CONTROL PARAMETERS WITH "ACCESS LEVEL 1"
Parameters of "Input/Output"
Screen Parameter
I01
TEMP_RET
I01
TEMP_EXT
I01a
TEMP_SONDA_AMB
I01a
SONDA_AMB_1_TEMP
I01a
SONDA_AMB_2_TEMP
I01a
SONDA_AMB_3_TEMP
I01a
SONDA_AMB_4_TEMP
I01a
SEL_TEMP_SONDAS_AMB_CALOR
I01a
SEL_TEMP_SONDAS_AMB_FRIO
I01b
TEMP_TCO
I02
HUM_SONDA_INT_RS485_O_AI10 Display of the ambient humidity RS485 probe (middle value)
I02
SONDA_AMB_1_HUM
I02
SONDA_AMB_2_HUM
I02
SONDA_AMB_3_HUM
I02
SONDA_AMB_4_HUM
I02a
HUM_EXT
I02b
Speed_Input_Rpm_FRIO_Fan1
I02b
Speed_Input_Rpm_CALOR_Fan1
I02b
Speed_Input_Rpm_VENTIL_Fan1
I02b
CAUDAL_VINT_MEDIDO_AJUSTE Measured fl ow rate at supply
I02b
actual_speed_msk_Fan1
I02b
SET_CAUDAL_VINT_FRIO
I02b
SET_CAUDAL_VINT_CALOR
SET_CAUDAL_VINT_
I02b
VENTILACION
I02b
Speed_Input_perc_FRIO_Fan1
I02b
Speed_Input_perc_CALOR_Fan1
I02b
Speed_Input_perc_VENTIL_Fan1
I02c
Speed_Input_Rpm_FRIO_Fan2
I02c
Speed_Input_Rpm_CALOR_Fan2
I02c
Speed_Input_Rpm_VENTIL_Fan2
I02c
CAUDAL_VRET_MEDIDO_AJUSTE Measured fl ow rate at return
I02c
actual_speed_msk_Fan2
I02c
SET_CAUDAL_VRET_FRIO
I02c
SET_CAUDAL_VRET_CALOR
SET_CAUDAL_VRET_
I02c
VENTILACION
I02c
Speed_Input_perc_FRIO_Fan2
I02c
Speed_Input_perc_CALOR_Fan2
I02c
Speed_Input_perc_VENTIL_Fan2
I03
TEMP_IMP
I03
TEMP_MEZCLA
I03a
CO2
I03a
CO2_FISICA_zona1
I03a
CO2_FISICA_zona2
I03a1
CO2
I03b
TEMP_ENTRADA_BAC
I03b
TEMP_SALIDA_BAC
I03c
TEMP_EXTRACCION_RUEDA
I03c
TEMP_RECUPERACION_RUEDA
I04a
ENTALPIA_EXT_KCAL
I04a
HUM_EXT
I04b
ENTALPIA_INT_KCAL
I04b
HUM_INT
I05a
T_P_HP_C1
I05a
TEMP_CAL_HP_C1
I05a
T_P_HP_C2
I05a
TEMP_CAL_HP_C2
36
E
Description of the parameter
Display of the return air temperature
Display of the outdoor air temperature
Display of the ambient air temperature (NTC or RS485)
Display of the ambient temperature probe No.1 - RS485
Display of the ambient temperature probe No.2 - RS485
Display of the ambient temperature probe No.3 - RS485
Display of the ambient temperature probe No.4 - RS485
Selection of the value of ambient temperature with RS485 probes
in HEATING mode (0 = middle, 1 = minimum, 2 = maximum)
Selection of the value of ambient temperature with RS485 probes
in COOLING mode (0 = middle, 1 = minimum, 2 = maximum)
Selection of the value of ambient temperature with User terminal 0.0
Display of the ambient humidity probe No.1 - RS485
Display of the ambient humidity probe No.2 - RS485
Display of the ambient humidity probe No.3 - RS485
Display of the ambient humidity probe No.4 - RS485
Display of the outdoor air humidity
rpm setpoint for control of supply fan in COOING mode
rpm setpoint for control of supply fan in HEATING mode
rpm setpoint for control of supply fan in VENTILATION
Current speed of supply fan
Setpoint for constant supply fl ow control in COOING mode
Setpoint for constant supply fl ow control in HEATING mode
Setpoint for constant supply fl ow control in VENTILATION
% setpoint for PWM control of supply fan in COOING mode
% setpoint for PWM control of supply fan in HEATING mode
% setpoint for PWM control of supply fan in VENTILATION
rpm setpoint for control of return fan in COOING mode
rpm setpoint for control of return fan in HEATING mode
rpm setpoint for control of return fan in VENTILATION
Current speed of return fan
Setpoint for constant return fl ow control in COOING mode
Setpoint for constant return fl ow control in HEATING mode
Setpoint for constant return fl ow control in VENTILATION
% setpoint for PWM control of return fan in COOING mode
% setpoint for PWM control of return fan in HEATING mode
% setpoint for PWM control of return fan in VENTILATION
Display of the supply air temperature
Display of the mixing air temperature
Display of the CO2 probe or the diff erence between indoor probe
and outdoor probe (in units with outdoor CO2 probe)
Reading of the CO2 probe of zone 1 (zoning into 2 zones)
Reading of the CO2 probe of zone 2 (zoning into 2 zones) or
second CO2 probe or outdoor CO2 probe
Display of the diff erential pressure sensor reading for air renewal
(Pa)
Display of the water inlet temperature of the hot water coil
Display of the water outlet temperature of the hot water coil
Display of the exhaust air temperature on the wheel
Display of the recovery air temperature on the wheel
Display of the outdoor enthalpy
Display of the outdoor air humidity
Display of the indoor enthalpy
Display of the indoor air humidity
Display of the high pressure transducer of circuit 1
Calculated temperature for high pressure of circuit 1
Display of the high pressure transducer of circuit 2
Calculated temperature for high pressure of circuit 2
INPUTS/OUTPUTS
Value Min.
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0
0
0
0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
1200 0
1200 0
1200 0
0
0
0
0
30600 0
30600 0
30600 0
50.0
0.0
50.0
0.0
50.0
0.0
1200 0
1200 0
1200 0
0
0
0
0
30600 0
30600 0
30600 0
50.0
0.0
50.0
0.0
50.0
0.0
0.0
-99.9
0.0
-99.9
0
-9999
0
-9999
0
-9999
0
-9999
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.999 99.999 Kcal/kg Integer R
0.0
-99.9
0.0
-99.999 99.999 Kcal/kg Integer R
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
0.0
-99.9
Add.
Max.
UOM
Type
R/W
BMS
99.9
°C
Analog. R
1
99.9
°C
Analog. R
2
99.9
°C
Analog. R
99.9
°C
Analog. R
193
99.9
°C
Analog. R
196
99.9
°C
Analog. R
241
99.9
°C
Analog. R
244
2
---
Analog. R
200
2
---
Analog. R
199
99.9
°C
Analog. R
14
99.9
%rH
Analog. R
5
99.9
%rH
Analog. R
194
99.9
%rH
Analog. R
197
99.9
%rH
Analog. R
242
99.9
%rH
Analog. R
245
99.9
%rH
Analog. R
6
2950
rpm
Integer R
275
2950
rpm
Integer R
277
2950
rpm
Integer R
279
99999 m
h
Integer R
198
3/
9999
rpm
Integer R
199
99999 m
h
Integer R
200
3/
99999 m
h
Integer R
201
3/
99999 m
h
Integer R
197
3/
100.0 %
Analog. R
160
100.0 %
Analog. R
161
100.0 %
Analog. R
159
2950
rpm
Integer R
276
2950
rpm
Integer R
278
2950
rpm
Integer R
280
99999 m
h
Integer R
204
3/
9999
rpm
Integer R
205
99999 m
h
Integer R
206
3/
99999 m
h
Integer R
207
3/
99999 m
h
Integer R
203
3/
100.0 %
Analog. R
175
100.0 %
Analog. R
176
100.0 %
Analog. R
174
99.9
°C
Analog. R
7
99.9
°C
Analog. R
8
9999
ppm
Integer R
3
9999
ppm
Integer R
256
9999
ppm
Integer R
220
9999
Pa
Integer R
3
99.9
°C
Analog. R
25
99.9
°C
Analog. R
26
99.9
°C
Analog. R
247
99.9
°C
Analog. R
249
14,15
99.9
%rH
Analog. R
6
16,17
99.9
%rH
Analog. R
5
99.9
bar
Analog. R
3
99.9
°C
Analog. R
123
99.9
bar
Analog. R
4
99.9
°C
Analog. R
124