12 - ALARMS
Controlled alarms
Gas burner or boiler
Thermistor of electrical heater for preheating
in the fresh air
Blocking the electrical heating contactor
Failure of Eprom memory of the μPC3 board
Failure of Eprom memory of the SMALL board
(zoning)
μPC3 board clock missing or not working
SMALL board clock missing or not working
(zoning)
unit maintenance (cumulative operating hours) No
Failure of return temperature probe
Failure of ambient humidity probe No.1
RS485 probe No.1 without communication
Failure of ambient temperature probe No.1
Failure of ambient humidity probe No.2
RS485 probe No.2 without communication
Failure of ambient temperature probe No.2
Failure of ambient humidity probe No.3
RS485 probe No.3 without communication
Failure of ambient temperature probe No.3
Failure of ambient humidity probe No.4
RS485 probe No.4 without communication
Failure of ambient temperature probe No.4
Failure of the indoor (return) humidity probe
Failure of the outdoor humidity probe
Failure of the supply temperature probe
Failure of the mixing temperature probe or the
air quality probe
COOLING setpoint < HEATING setpoint
COOLING setpoint < HEATING setpoint in
zone 1
COOLING setpoint < HEATING setpoint in
zone 2
COOLING setpoint < HEATING setpoint in
zone 3
COOLING setpoint < HEATING setpoint in
zone 4
Anti-fi re safety device / smoke detection
Supply temperature limit exceeded
c.pCOe expansion card addr. 8 without
communic.
c.pCOe expansion card addr. 8 alarm mismatch No
c.pCOe expansion card address 9 without
communication
c.pCOe expansion card addr. 9 alarm mismatch No
Energy meter without communication
Supply plug-fan addr.1 without communication No
(*) If a certain number of alarms take place over a period of time, this reset can be changed to "Manual" (confi gurable by parameters).
(**) Alarm levels with "Backup". Please refer to the meaning in the following section.
Unit
Aff ected circ.
Reset
shutdown
shutdown
Type
Yes,
Yes
Auto (*) Yes, 4 s
all circuits
No
No
Auto (*)
Yes
Yes
Manual No
No
No
Manual No
No
No
Manual No
No
No
Manual No
No
No
Manual No
No
Manual No
Yes
Yes
Manual No
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
No
No
Auto
Yes
Yes
Manual No
Yes
Yes
Auto
Yes
Yes
Auto
Yes
Yes
Auto
Yes
Yes
Auto
Yes,
Yes
Manual No
all circuits
No
No
Manual No
No
No
Auto
No
Auto
No
No
Manual No
No
Auto
No
No
Auto
No
Auto
Timing
Actuation
Only indication (safety into the
burner/boiler)
Unit / compressor shutdown
(confi gurable by parameter)
Locking by repeated alarms
Yes,14 s
Shutdown of electrical heater for
(progr.)
preheating in the fresh air
Unit shutdown and ventilation
mode at maximum fl ow
Serious alarm
Serious alarm, but only indication 1
Only indication
Only indication
Only indication
Serious alarm, unit shutdown
Yes,10 s
Only indication
(progr.)
Yes,
Only indication
10 s
Stop zone 1 (air fl ow zoning)
Yes,10 s
Only indication
(progr.)
Stop zone 1 (air fl ow zoning)
Yes,
10 s
Only indication
(progr.)
Yes,
Only indication
10 s
Stop zone 2 (air fl ow zoning)
Yes,10 s
Only indication
(progr.)
Stop zone 2 (air fl ow zoning)
Yes,10 s
Only indication
(progr.)
Yes,
Only indication
10 s
Stop zone 3 (air fl ow zoning)
Yes,10 s
Only indication
(progr.)
Stop zone 3 (air fl ow zoning)
Yes,10 s
Only indication
(progr.)
Yes,
Only indication
10 s
Stop zone 4 (air fl ow zoning)
Yes,10 s
Only indication
(progr.)
Stop zone 4 (air fl ow zoning)
No
Only indication
No
Only indication
No
Only indication
No
Only indication
Serious alarm, unit shutdown
No
Unit shutdown (air fl ow zoning)
No
Unit shutdown (air fl ow zoning)
No
Unit shutdown (air fl ow zoning)
No
Unit shutdown (air fl ow zoning)
Serious alarm, shut-down of
the unit and fresh air damper
open / closed (confi gurable by
parameter)
Shutdown of electrical heaters or
gas burner/boiler
No
Only indication
No
Only indication
Unit shutdown and dampers on
the previous position to the alarm
(zoning 2 zones)
No
Only indication
No
Only indication
No
Only indication
Alarm
Graphic
User
Add.
level (**)
terminal
terminal
3 or 2
AL24
AL24
44
3
AL24a
AL2401
297
3
AL24b
AL2402
354
3
AL26
AL26
32
AL26zn
---
1
AL27
AL27
33
0
AL27zn
---
3 or 1
AL28
AL28
108
0
AL29
AL29
109
0
AL30a
AL3001
165
0
AL30b
AL3002
163
0
AL30c
AL3003
164
0
AL30d
AL3004
177
0
AL30e
AL3005
175
0
AL30f
AL3006
176
0
AL30g
AL3007
259
0
AL30h
AL3008
257
0
AL30i
AL3009
258
0
AL30j
AL3010
262
0
AL30k
AL3011
260
1
AL30l
AL3012
261
1
AL33
AL33
112
1
AL34
AL34
113
1
AL35
AL35
114
1
AL35a
AL3501
130
3
AL36
AL36
115
0
AL36a
---
360
0
AL36b
---
361
0
AL36c
---
362
0
AL36d
---
363
3
AL39
AL39
136
3
AL40
AL40
166
0
AL45b
AL4502
211
0
AL45g
AL4507
210
0
AL45c
AL4503
---
0
AL45h
AL4508
---
0
AL46
AL46
192
1
AL47
AL47
201
27