Daikin EPRA14DAW1 Installer's Reference Manual page 180

Hide thumbs Also See for EPRA14DAW1:
Table of Contents

Advertisement

9
|
Configuration
Emergency
Glycol filled system
Balancing
Installer reference guide
180
Emergency
To keep energy consumption low, we recommend to set Emergency to auto SH
reduced/DHW off if the house is unattended for longer periods.
#
Code
[9.5.1]
[4-06]
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface
only.
INFORMATION
If a heat pump failure occurs and Emergency is set to Manual, the room frost
protection function, the underfloor heating screed dryout function, and the water
pipe antifreeze function will remain active even if the user does NOT confirm
emergency operation.
HP forced off
HP forced off mode can be activated to allow the backup heater to provide
domestic hot water and space heating. Cooling is NOT possible when this mode is
activated.
#
Code
[9.5.2]
[7-06]
Glycol Filled system
This setting gives the installer the possibility to indicate whether the system is filled
with glycol or water. This is important in case glycol is used to protect the water
circuit against freezing. If NOT set correctly, the liquid in the piping can freeze.
#
Code
N/A
[E-0D]
Priorities
For systems with an integrated domestic hot water tank.
Description
0: Manual
1: Automatic
2: auto SH reduced/DHW on
3: auto SH reduced/DHW off
4: auto SH normal/DHW off
Description
Activation of the HP forced off mode:
0: disabled
1: enabled
Description
Glycol Filled system: Is the system filled
with glycol?
0: No
1: Yes
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1A – 2020.01

Advertisement

Table of Contents
loading

Table of Contents