9
|
Configuration
Installer reference guide
154
Setpoint range
For more information about Setpoint range, see
#
Code
Leaving water temperature range for the main leaving water temperature zone (=
the leaving water temperature zone with the lowest leaving water temperature in
heating operation and the highest leaving water temperature in cooling
operation)
[2.8.1]
[9-01]
[2.8.2]
[9-00]
[2.8.3]
[9-02]
[2.8.4]
[9-03]
Control
The control type for the additional zone is read only. It is determined by the control
type of the main zone.
4
See
"9.5.3 Main
zone" [
#
Code
[3.9]
N/A
Thermostat type
Only applicable in external room thermostat control.
Also see
"9.5.3 Main
zone" [
#
Code
[3.A]
[C‑06]
Leaving water temperature: Delta T
For more information, see
Heating minimum:
15°C~37°C
Heating maximum:
[2‑0C]=2 (emitter type main zone = radiator)
37°C~70°C
Otherwise: 37°C~55°C
Cooling minimum:
5°C~18°C
Cooling maximum:
18°C~22°C
 140].
Control:
Leaving
water if the control type of the
main zone is Leaving water.
External room thermostat if the control
type of the main zone is:
-
External room thermostat,or
-
Room thermostat.
4
 140].
External room thermostat type for the additional
zone:
1: 1
contact. Connected to only 1 digital
input (X2M/35a)
2: 2 contacts. Connected to 2 digital inputs
(X2M/34a and X2M/35a)
4
"9.5.3 Main
zone" [
 140].
"9.5.3 Main
zone" [
Description
Description
Description
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1A – 2020.01
4
 140].