Note
Check whether the float is present in the
condensate trap.
6.
Clip the lower section of the condensate trap (1) into the
upper section of the condensate trap (2).

11.10 Installing the gas-air mixture unit

1.
Install the burner.
2.
Install two new burner seals in the burner hood.
3.
Install the gas-air mixture unit.
4.
Tighten the screws on the gas-air mixture unit.
Ideally to 7 Nm if a torque spanner is available.
5.
Install the flue pipe.
6.
Install the air intake pipe.

11.11 Draining the product

1.
Close the service valves of the product.
2.
Start check programme P.05.
Overview of the check programmes (→ Page 14)
3.
Open the drain valves.
11.12 Checking the admission pressure of the
expansion vessel
1.
Drain the product. (→ Page 27)
2.
Measure the pre-charge pressure of the expansion ves-
sel at the vessel valve.
Conditions: Pre-charge pressure < 0.075 MPa (0.75 bar)
Top up the expansion vessel in accordance with the
static height of the heating installation, ideally with ni-
trogen, otherwise with air. Ensure that the drain valve is
open when topping up.
3.
If water escapes from the valve of the expansion
vessel, you must replace the expansion vessel
(→ Page 23).
4.
Fill and purge the heating installation. (→ Page 16)
11.13 Completing inspection and maintenance
work
1.
Check the gas connection pressure (gas flow pressure).
(→ Page 17)
2.
Check the CO₂ content. (→ Page 18)

11.14 Checking the product for leak-tightness

Check that the product is leak-tight. (→ Page 19)

12 Decommissioning the product

Switch off the product.
Disconnect the product from the electrical installation.
Close the gas stopcock.
Close the cold-water isolation valve.
Drain the product. (→ Page 27)
0020277252_00 ecoFIT sustain Installation and maintenance instructions
Decommissioning the product 12

13 Customer service

To ensure regular servicing, it is strongly recommended
that arrangements are made for a Maintenance Agreement.
Please contact Vaillant Service Solutions for further details:
Telephone: 0330 100 3461
27