Horizontal Terminal Positioning - Vaillant ecoFIT sustain 615 Installation And Maintenance Instructions Manual

Hide thumbs Also See for ecoFIT sustain 615:
Table of Contents

Advertisement

Installation site
M
Vertical from a terminal on the same wall
N
Horizontal from a terminal on the same wall
O
From the wall on which the terminal has been installed
P
From a vertical structure on the roof
Q
Above the roof area
R
Horizontal from adjacent windows on pitched or flat roofs
S
Above adjacent windows on pitched or flat roofs
T
Below adjacent windows on pitched or flat roofs
G.2

Horizontal terminal positioning

BS 5440-1 recommends that fanned flue chimney terminals should be positioned as follows:
a) at least 2 m from an opening in the building directly opposite, and
b) so that the products of combustion are not directed to discharge directly across a boundary if the products are likely to
cause a nuisance to a neighbour or discharge over a walkway or patio.
For IE see current issue of IS 813.
For boilers covered within this manual.
1) Dimensions D, E, F and G:
These clearances may be reduced to 25 mm without affecting the performance of the boiler. In order to ensure that the con-
densate plume does not affect adjacent surfaces the terminal should be extended as shown below.
Adequately secured
The flue pipe must
protrude beyond any overhang
air/flue gas pipe
2) Dimension H:
This clearance may be reduced to 25 mm without affecting the performance of the boiler. However, in order to ensure that
the condensate plume does not affect adjacent surfaces a clearance of 300 mm is preferred.
For 1 and 2 above you can use a flue gas management kit to enable the termination point to be positioned and directed away
from the building fabric.
0020277252_00 ecoFIT sustain Installation and maintenance instructions
Balcony/eaves
Gutter
Appendix
Minimum dimen-
sions
1,500 mm
300 mm
0 mm
300 mm
300 mm
600 mm
600 mm
2,000 mm
39