Event History Submenu; Configuration Submenu - Kohler 14EKOZD Operation

Marine generator sets
Hide thumbs Also See for 14EKOZD:
Table of Contents

Advertisement

Genset Spec No. displays the generator set specification number. Only adjustable from SiteTech™.
Genset Serial No. displays the generator set serial number. Only adjustable from SiteTech™.
Alternator Part No. displays the alternator part number. Only adjustable from SiteTech™.
Engine Part No. displays the engine part number. Only adjustable from SiteTech™.
Engine Model No. displays the engine model number. Only adjustable from SiteTech™.
Engine Serial No. displays the engine serial number. Only adjustable from SiteTech™.

2.11.2 Event History Submenu

Generator Event History:
This menu allows the user to review up to 1000 entries of generator system events including shutdown faults, warning faults,
notices, and status events with date and time stamp. See Controller Fault Diagnostics section for a list of the items that appear
on the Generator Event History.
Engine Event Log:
A message is sent each time there is a change in a monitored engine condition (i.e. fault becomes active, fault is cleared). Upon
broadcast of this message, the controller will request another message that contains the following information for each fault:
SPN (Suspect Parameter Number) is a four-digit code that represents an engine component.
FMI (Failure Mode Indicator) is a two-digit code that represents the type of fault that occurred (i.e. short circuit, out of
range).
Occurrence Count is a count of how many times a fault has occurred.

2.11.3 Configuration Submenu

Generator Configuration
The values in this menu are user-entered for the generator set configuration and are NOT measured values of the generator
set.
Note:
Have setup and adjustments of the Decision-Maker
The setup and adjustments are password protected.
Operating Mode displays the programmer entered generator set application configuration as Standby or Prime.
Application Type displays the programmer entered generator set application type as None, Marine, Mobile, Standby
or Prime.
System Voltage displays the programmer-entered L1-L2-L3 output voltage for three-phase or the L1-L2 output voltage
for single-phase.
System Frequency displays the programmer-entered L1-L2-L3 output voltage frequency for three-phase or the L1-L2
output voltage frequency for single-phase.
System Phase displays the programmer-entered configuration as Single Phase, Single Phase Dogleg, Three Phase
Wye, or Three Phase Delta.
Rated Engine Speed displays the programmer entered engine speed in RPM.
Adjusted Engine RPM displays the target engine speed setting.
kW Rating displays the programmer entered kW value for the generator set.
kVA Rating displays the programmer entered kVA value for the generator set.
Rated Current displays the programmer entered current value for the generator set.
Battery Voltage displays the programmer entered battery voltage.
TP-7044
6/23
®
3500 controller performed only by an authorized Kohler distributor/dealer.