Application planning
4.2 Location planning
Minimum clearances for wall/ceiling mounting
For operation and maintenance and to ensure proper ventilation of the
SICHARGE UC Dispenser, you must maintain the following minimum clearances (in mm):
For the option with an air-conditioning unit, take into account a sufficient distance from the
top edge to the room ceiling to prevent a heat build-up.
Figure 4-4  Minimum clearances for wall/ceiling mounting front view
Maximum allowable temperature at air inlet
The maximum permissible ambient temperature is 45 °C. When the ambient temperature
exceeds 45 °C, the charging capacity is reduced (derating).
With the optional air-conditioning unit, the maximum permissible ambient temperature is
55 °C.
36
SICHARGE UC Dispenser
Operating Instructions, 06/2023, A5E50235695-AE