Pilot Flame Characteristics - Empire Comfort Systems VFP36SP32E Installation Instructions And Owner's Manual

Premium vent-free multi-sided fireplaces
Table of Contents

Advertisement

Figure 20 show a correct pilot flame pattern. The correct flame will
be blue and will extend beyond the thermocouple. The flame will
surround the thermocouple just below the tip. A slight yellow flame
may occur where the pilot flame and main burner flame meet. Figure
21 show an incorrect pilot flame pattern. The incorrect pilot flame
is not touching the thermocouple. This will cause the thermocouple
to cool. When the thermocouple cools, the heater will shut down.
THERMOPILE
THERMOCOUPLE
(LPG)
Correct Pilot Flame Pattern
THERMOPILE
THERMOCOUPLE
(LPG)
Incorrect Pilot Flame Pattern
If pilot flame pattern is incorrect, as shown in Figure 21
See Troubleshooting, page 24.
39813-1-0919

PILOT FLAME CHARACTERISTICS

PILOT
THERMOCOUPLE
(NATURAL)
Figure 20
PILOT
THERMOCOUPLE
(NATURAL)
Figure 21
Cleaning and Pilot Maintenance
Oxygen Depletion Sensor Pilot - Figure 22
When the pilot has a large yellow tip flame, clean the Oxygen
Depletion Sensor as follows:
1. Clean the ODS pilot by loosening nut B from the pilot tubing.
When this procedure is required, grasp nut A with an open end
wrench.
2. Blow air pressure through the holes indicated by the arrows.
This will blow out foreign materials such as dust, lint and spider
webs. Tighten nut B also by grasping nut A.
B
A
Never use needles, wires, or similar cylindrical objects to
clean the pilot to avoid damaging the calibrated ruby that
controls the gas flow.
Figure 22
WARNING
Page 23