Mantel Requirements; Combustible Mantels - Lopi 864 TV 40K CleanFace Installation Manual

Direct vent fireplace
Table of Contents

Advertisement

Finalizing the Installation

Mantel Requirements

Combustible Mantels

Use the table below to determine the maximum mantel depth allowed. The mantel depth (measured
from the face of the fireplace) must fall in the shaded portion of the table.
Any material that protrudes more than 3/4" (19mm) from the non-combustible facing is considered a
mantel and must meet the mantel requirements.
50-3/4"+ (1290mm)
49-3/4" (1264mm)
Mantel Height
48-3/4" (1239mm)
Above Base of
47-3/4" (1213mm)
46-3/4" (1188mm)
Fireplace (a)
45-3/4" (1163mm)
44-3/4" (1137mm)
43-3/4" (1112mm)
Mantel (combustible or non-
combustible)
© Travis Industries
Maximum Mantel Depth (b)
b
a
Base of the Fireplace
(for qualified installers only)
Combustible mantel columns (legs) must
be placed to the side of the fireplace face.
Non-combustible mantel columns do not
have a minimum clearance.
6/28/2019 - 1499
31